P-band of control
(Xp)
87
Integral action time
of control (Tn)
en
Block "Setpoint of return temperature limitation"
101 Simulation of out-
side temperature
Block "Service functions and general settings"
161 Simulation of out-
side temperature
162 Relay test
163 Sensor test
SET = setpoint or
limit value
ACTUAL = actual
value
= short-circuit
= interruption
164 Test of H-contacts
= contact is
closed
= contact is
open
Building Technologies
32.0 °C
(1.0...100.0)
...................
120 s
(10...873)
......................
--- °C
(--- / 0...140)
...................
--.- °C
(--.- / −50...+50)
...................
0
(0...4)
Display function
Display function
74 319 0620 0 a
°C
s
Setting --- = function disabled
°C
Simulation will automatically be
°C
terminated after 30 min
--.- = no simulation
0 = normal operation
1 = all contacts open
2 = heating circuit valve OPENS
Y1
3 = heating circuit valve
CLOSES Y2
4 = heating circuit pump / circu-
lating pump ON M1
To terminate the relay test:
Select next line, or automatically
after 30 minutes
0 = outside sensor B9
1 = flow sensor B1
2 = room sensor at terminal B5
3 = room unit sensor at terminal
A6
4 = return sensor B7
H1 = overriding the operation
mode
H2 = manually generated heat
demand
17.04.2008
30/152