Descargar Imprimir esta página

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

T
ECHNICAL DATA TABLE
MODELS
INPUT
Nominal voltage
Nominal frequency
Accepted range
Voltage and frequency range for non
intervention of the battery
(1)
Maximum current
(2)
Nominal current
Power factor
Current distortion @ maximum load
BYPASS
Accepted voltage range for switching
Accepted frequency range for switching
Switching time
BATTERY
No. batteries / V / Ah
(8)
Recharge time
OUTPUT
(7)
Nominal voltage
Maximum current
(3)
Static variation
(4)
Dynamic variation
Waveform
Voltage distortion @ linear load
Voltage distortion @ distorting load
(5)
Frequency
Current crest factor
Nominal power
Nominal power
MISCELLANEOUS
Leakage current to earth
AC/AC efficiency
(6)
Ambient temperature
Humidity
Protections
Hold-up time
Noise level
Dimensions H x L x D
Weight
68
SDL 5000
[Vac]
[Hz]
[Vac]
[Vac]
Maximum: 276
[Vac]
Minimum: 164 ÷ 84
[Vac]
Return to mains-powered operation: 180
[Hz]
Frequency: 40 ÷ 72
[A]
25
[A]
18
[Vac]
Frequency selected ±5 %
[msec]
16 / 12 / 7 high rate discharge
[h]
[Vac]
[A]
23 / 22 / 21
[VA]
5000
[W]
3500
[mA]
[°C]
Excessive battery discharge – Overcurrent – short-circuit –
Overvoltage – undervoltage - thermal
[msec]
[mm]
[Kg]
SDL 6000
220 - 230 - 240
50 – 60
0 ÷ 276
(from 100% to 50% of load in
linear mode)
30
22
0.98
6%
180 ÷ 264
0,1
4 ÷ 6
220 / 230 / 240 ±1.5%
27 / 26 / 25
1.5%
5% in 20 msec
Sinusoidal
3%
5%
50 or 60 Hz selectable
3 : 1
6000
4200
2
> 91%
0 – 40
< 90% non-condensing
35
< 45 dB(A) at 1 mt.
(9)
455 x 175 x 660
64

Hide quick links:

Publicidad

loading

Este manual también es adecuado para:

Sentinel dual sdl 6000