5.4 Technical data table
Factory settings
The unit is factory-set to 80% power.
A
Technical data
The column on the right gives the abbreviation used on the dataplate.
Data
Max. heating capacity
Min. heating capacity
Max. Heat Output in heating (80/60°C)
Min. Heat Output in heating (80/60°C)
Max. Heat Output in heating (50/30°C)
Min. Heat Output in heating (50/30°C)
Efficiency Pmax (80-60°C)
Efficiency Pmin (80-60°C)
Efficiency Pmax (50-30°C)
Efficiency Pmin (50-30°C)
Efficiency 30%
Gas supply pressure G20
Max. gas delivery G20
Min. gas delivery G20
Gas supply pressure G31
Max. gas delivery G31
Min. gas delivery G31
Efficiency class Directive 92/42 EEC
NOx emission class
Max. working pressure in heating
Min. working pressure in heating
Max. heating temperature
Heating water content
Protection rating
Power supply voltage
Electrical power input
Empty weight
Type of unit
PIN CE
88
EN
Unit
ENERGY TOP B 80
ENERGY TOP B 125
kW
75.0
kW
17.0
kW
73.5
kW
16.7
kW
79.5
kW
18.3
%
98.0
%
98.5
%
106
%
107.5
%
109
mbar
20
3
7.94
m
/h
3
1.8
m
/h
mbar
37
kg/h
5.87
kg/h
1.33
-
-
5
bar
6
bar
0.8
°C
95
litres
13
IP
X5D
V/Hz
230V/50Hz
W
225
kg
110
cod. 3541H060 - Rev. 02 - 04/2018
ENERGY TOP B
ENERGY TOP B 160
116.0
150.0
25.0
17.0
113.7
147.0
24.6
16.7
123.0
159.0
26.9
18.3
98.0
98.0
98.5
98.5
106
106
107.5
107.5
109
109
20
20
12.38
15.88
2.65
1.8
37
37
9.08
11.74
1.96
1.33
5
5
6
6
0.8
0.8
95
95
15
26
X5D
X5D
230V/50Hz
230V/50Hz
330
315
115
190
B23
0461BS0879
ENERGY TOP B 250
232.0
(Q)
25.0
(Q)
227.4
(P)
24.6
(P)
246.0
26.9
98.0
98.5
106
107.5
109
20
24.76
2.65
37
18.16
1.96
5
(NOx)
6
(PMS)
0.8
95
(tmax)
30
X5D
230V/50Hz
427
210