SPM Chlorine = 20 strokes
BP Chlorine = 0.20 ppm
NB. The SPM parameter must not be greater than the maximum number of pulses per minute
accepted by the pump.
7.7___SET POINT FUNCTION
With the
key, the user can display the
SET POINTs cyclically, and he can then use the
and
keys to change them without
having to enter the programming mode.
If protection is provided on the terminal strip, and
step EN has been programmed as –C o --, then
it is only possible to use the
key to display the SET POINTs without being able to change
them.
7.8___MANUAL CONTROL AND PRIMING
THE PUMPS.
Keeping the
key depressed, it is possible
to activate the relays controlling the pH and
chlorine pumps in sequence by pressing the
key at the same time.
This function is useful for operations for priming the pumps.
7.9___FLOW ALARM
A flow sensor is connected to terminals 13 and 14. The sensor is positioned in the piezometric
overflow device of the POOL TOP system. If the flow of water drops so much that measurement is
prejudiced, the instrument is triggered, stopping chlorination and generating an alarm.
The flow alarm is activated if the gating remains active uninterruptedly for 40 seconds . In this
case, in addition to seeing the alarm LED flashing on the pH measurement display, the indication
FLUS will appear, alternating with the measured value.
N.B. In the flow alarm status, the current outputs are forced to 0 mA.