Descargar Imprimir esta página

Electrical Connections - Ferroli QUADRIFOGLIO B Instrucciones De Uso, Instalación Y Mantenimiento

Ocultar thumbs Ver también para QUADRIFOGLIO B:

Publicidad

Idiomas disponibles

Idiomas disponibles

QUADRIFOGLIO B
Generators in cascade: one direct heating circuit and one DHW circuit with circu-
lating pump
Schematic diagram
The boiler's electronics can manage up to 6 modules. 3 are given in the example.
M

Electrical connections

After installation, carry out the necessary electrical connections as shown on the wiring
diagram.
Then configure the controller as described in the specific section.
MASTER
1
2
3
4
5
6
7
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
72
138
298
37 38 39 40 41 42 43 44
SLAVE 1
1
2
3
4
5
6
7
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44
SLAVE 2
1
2
3
4
5
6
7
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44
M
M
fig. 48
8
9
10 11 12 13 14 15 16 17 18
A C
300M
B
155
L
N
8
9
10 11 12 13 14 15 16 17 18
A C
300S
B
L
N
8
9
10 11 12 13 14 15 16 17 18
A C
300S
B
L
N
fig. 49
cod. 3541F574 - Rev. 00 - 09/2017
Legend
72 Room thermostat 1st zone (direct)
130 Hot water tank circulating pump
138 External probe
155 Hot water tank probe
298 Cascade temperature sensor
300M MASTER boiler motor-operated butterfly valve
A = OPENING PHASE
B = NEUTRAL
C = CLOSING PHASE
300S SLAVE boiler motor-operated butterfly valve
A = OPENING PHASE
B = NEUTRAL
C = CLOSING PHASE
I* ISPESL safety devices (When required - not supplied)
To manage sliding temperature it is necessary to purchase the external probe accessory code 013018X0
If a hot water tank probe (not supplied) is used, it is necessary to purchase the NTC probe accessory code
1KWMA11W (2 mt.) or code 043005X0 (5 mt.)
If a hot water tank thermostat (not supplied) is used, it is necessary to purchase the kit accessory code
013017X0 (to be connected in place of the Hot Water Tank Probe)
If a cascade probe (not supplied) is used, it is necessary to purchase the NTC probe accessory code
1KWMA11W (2 mt.) or code 043005X0 (5 mt.)
Parameters
Each system requires a different parameterisation. Follow the access procedure given
below, for the MASTER as well as SLAVE boilers.
"Service Menu"
Check/Change parameter P02 of the "Transparent Parameters Menu" to 8. (for models
B 70, B 125 and B 320) and to 5 (for model B 220)
Check/Change parameter b08 of the "Transparent Parameters Menu" to 3.
"System Type Menu"
Change parameter P.02 of the "System Type Menu" to 1.
Change parameter P.09 of the "System Type Menu" to 1.
- Optional functions
As well as the electrical connections of the previous figure (required for this system con-
figuration) there are options that do not require settings.
1
2
3
4
5
6
7
L
N
302
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
134
37 38 39 40 41 42 43 44
fig. 50 - MASTER
306 1st zone (direct) circulating pump
a 1st zone (direct)
b Hot water tank circuit
M Delivery
RA High Temperature Return
RB Low Temperature Return
8
9 10 11 12 13 14 15 16 17 18
N
EN
357
L
75

Publicidad

loading