CONTROLLO ZONE FZ4B
"TS" - TRANSPARENT PARAMETERS MENU
The zone controller is equipped with 38 transparent parameters also modifi able from Remote Control (Service Menu):
Boiler Board
Com.Rem. Board FZ4B
(If arr.)
01
P01
02
P02
03
P03
04
P04
o01
05
P05
o02
06
P06
07
P07
08
P08
09
P09
10
P10
o03
11
P11
o04
12
P12
13
P13
14
P14
15
P15
16
P16
o05
17
P17
o06
18
P18
19
P19
20
P20
21
P21
22
P22
23
P23
24
P24
25
P25
26
P26
27
P27
28
P28
29
P29
30
P30
31
P31
32
P32
33
P33
34
P34
35
P35
36
P36
37
P37
38
P38
Press the + and - buttons to scroll the list of parameters in increasing or decreasing order respectively. To modify the value of a parameter, just press the Ok button after
selecting it: press the + and - buttons to modify it; the setting will be automatically saved. Press the Ok button to return to the list of parameters. Press the Ok button for 3
seconds to return to the Service Menu. Press the Ok button for 5 seconds to exit the card Service Menu, or exiting occurs automatically after 15 minutes.
"IN" - INFORMATION MENU
The card can display the following information:
t01 NTC sensor (T1)
t02 NTC sensor (T2)
t03 NTC sensor (T3)
t04 NTC sensor (T4)
t05 On/Off Thermostat request or Room temperature measured by Remote Control (RT1)
t06 On/Off Thermostat request or Room temperature measured by Remote Control (RT2)
t07 On/Off Thermostat request or Room temperature measured by Remote Control (RT3)
t08 Zone1 Heating set point (Calculation)
t09 Zone2 Heating set point (Calculation)
t10 Zone3 Heating set point (Calculation)
t11 Zone Card Heating set point (Calculation)
Press the + and - buttons to scroll the list of information in increasing or decreasing order respectively. To display the value of a parameter, press the Ok button after
selecting it: in case of damaged Sensor, the card will display hyphens. Press the Ok button to return to the list of parameters. Press the Ok button for 3 seconds to return
to the Service Menu. Press the Ok button for 5 seconds to exit the card Service Menu, or exiting occurs automatically after 15 minutes.
"HI" - HISTORY MENU
The card can store the last 10 faults: the History datum item H1 represents the most recent fault that occurred, whereas the History datum item H10 represents the least recent.
The codes of the faults saved are also displayed in the corresponding menu of the Remote Control.
Press the + and - buttons to scroll the list of faults. To display the value of a parameter, press the Ok button after selecting it.
Press the Ok button for 3 seconds to return to the Service Menu. Press the Ok button for 5 seconds to exit the card Service Menu, or exiting occurs automatically after 15
minutes.
116
Description of Transparent Parameters
Zone1 Min. Temperature
Zone1 Max. Temperature
Zone1 calculated setpoint offset
Not implemented
Zone1 External Probe Curve
Zone1 External Probe Offset
Zone2 Min. Temperature
Zone2 Max. Temperature
Zone2 calculated set point offset
Not implemented
Zone2 External Probe Curve
Zone2 External Probe Offset
Zone3 Min. Temperature
Zone3 Max. Temperature
Zone3 calculated setpoint offset
Not implemented
Zone3 External Probe Curve
Zone3 External Probe Offset
Mixing valve on+off time (Only for Mixed Zones)
Mixing valve Boost (Only for Mixed Zones)
Mixing valve on+off time for °C (Only for Mixed Zones)
Hot water tank hysteresis
Hot water tank Primary setpoint (Excluding "Stand Alone 1" confi gurations)
Pump start temperature (Excluding "Stand Alone 1" confi gurations)
Hot water tank priority
Hot water tank setpoint (Only without Remote Control)
Post-circulation time
Zone pumps status with boiler in DHW mode (Only for "Communicating" confi gurations with DHW)
Delay for Zone
Equal settings for each zone
Mixing valve Closing time
Heating hysteresis (Only for "Stand Alone 2" confi gurations)
Heating standby time (Only for "Stand Alone 2" confi gurations)
Pump activation with card in standby
Heating delivery probe enabling (Only for "Stand Alone 2" confi gurations)
Operation with boiler in fault status
Legionella protection
Boiler Summer/Winter mode
between 05 and 125 °C
between 05 and 125 °C
between 05 and 125 °C
between -30 and 70°C (Negative values fl ash)
ON/OFF or between 05 and 125 °C
ON/OFF or between 05 and 125 °C
ON/OFF or between 05 and 125 °C
between 05 and 125 °C
between 05 and 125 °C
between 05 and 125 °C
between 05 and 125 °C
EN
Range
Default
20-90°C
20°C
20-90°C
40°C
0-40°C
10°C
10-90°C
90°C
0-10
0
20-40°C
30°C
20-90°C
20°C
20-90°C
40°C
0-40°C
0°C
10-90°C
90°C
0-10
0
20-40°C
30°C
20-90°C
20°C
20-90°C
80°C
0-40°C
0°C
10-90°C
90°C
0-10
0
20-40°C
30°C
0-15sec
15
0-120sec
0sec
00-15°C/sec 1sec/°C
0-20°C
4°C
70-85°C
80°C
0-60°C
0°C
0=Off, 1=On
0=Off
10-65°C
55°C
0-20min
10min
0=Off, 1=On
0=Off
0-255sec
30sec
0=Off, 1=On
0=Off
0-3min
3min
0-10°C
5°C
0-10min
2min
0=Off, 1=On
0=Off
0=Off, 1=On
0=Off
0=Off, 1=On
0=Off
0=Off, 1-7
0=Off
0=On, 1=Off
0=On