Aquasana Sterilight SC200-A Manual Del Propietário página 8

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

7. Once it is determined that there are no leaks, plug the system into the ground fault interrupter and check controller to
ensure the system is operating properly. The controller should illuminate without any alarms.
Note: DO NOT look directly at the glowing UV lamp.
8. Allow the water to run for a few minutes to clear any air or dust that may be in the chamber.
Note: When there is no flow, the water in the cell will become warm, as the UV lamp is always on. To remedy this, run a
cold water tap anywhere in the house for a minute to flush out the warm water.
3.1 Disinfection Procedure
UV disinfection is a physical disinfection process and does not add any potentially harmful chemicals to the water. As UV
does not provide a disinfection residual, it is imperative that the entire distribution system located after the UV be chemically
disinfected to ensure that the plumbing system is free from any bacteriological contaminants. The disinfection process must
be performed immediately after the UV unit is installed and repeated thereafter whenever the UV is shut down for service,
without power, or inoperative for any reason. The procedure for sanitizing the plumbing system is readily accomplished as
follows:
1
• Ensure the controller is
plugged in for entire
disinfection process.
5
2
1
2
• Turn on the cold water
supply.
• Open each faucet and all
water openings until you
smell the bleach and then
Notes: 1) The addition of chlorine (bleach) to a hot water tank that has in the past been fed with untreated raw water with
high levels of other contaminants (iron, manganese, hydrogen sulphide, organics, etc.) will result in oxidation
of these contaminants and may require repeated flushing of the hot water tank. This contingency must be
dealt with independently under the start-up procedure for any other conditioners that may form a part of the
pre-treatment for the UV unit.
2) The above disinfection procedure will result in a massive chlorine residual far in excess of the 0.5 to 1.0 mg/L
typically present in municipally chlorinated water and of a magnitude consistent with the minimum 50 mg/L
chlorine solution recommended for the disinfection of distribution systems known to be contaminated. Do not
consume water until complete system has been flushed.
2
2
2
• Shut off the water supply.
• Close each faucet.
6
2
2
2
2
• Turn on the hot water supply.
• Open each faucet and all
water openings until you
smell the bleach and then
close the faucets.
3
1
1
2
2
• Remove filter cartridge(s).
7
1
2
2
• DO NOT use water for 30
minutes.
• Flush the system until no
chlorine smell is detectable
and reinstall the filter
cartridge(s).
Installation of UV Disinfection System
2
• Pour 2 cups of household
• Re-install the housing(s).
1
30 mins
2
3
4
2
x2
bleach solution into the filter
housing(s).
Note: DO NOT use
Hydrogen Peroxide.
8

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Sterilight sc410-a

Tabla de contenido