BSP B/M/V _ _ _ - _ _ _ _ _ - P00S2B - S4(- _ _ _ )
Pressure Sensors with IO-Link

Menu functions

(The firmware version (e.g. N007) is displayed for approx.
2 seconds after the device is turned on.)
First menu level
Menu 1
Setting the switchpoints
and
Setting the respective value starting at
Menu 3
which Switchpoint 1 or 2 should be
/
activated. If the window function is enabled
SP 1
SP 2
/
in Menu 5/6 or 6/7, the value of the
F H 1
F H 2
switchpoint is the pressure upper limit of
the window (WindowHigh).
Menu 2
Setting the reset points
and
Setting the respective value starting at
Menu 4
which Reset Point 1 or 2 should be
/
activated. If the window function is enabled
r P 1
r P 2
/
in Menu 5/6 or 6/7, the value of the reset
F L 1
F L 2
point is the pressure lower limit of the
window (WindowLow). The reset point
must always lie below the value of the
associated switchpoint.
(Auxiliary
If Output Signal 2 is active (5/17)
menu)
Analog Output 2 (Offset ±5 % of measuring
/
ASt 2
AE n2
range) / Analog Output 2 (End Point
90...100 % of measuring range), e.g. for a
sensor with measuring range 0...10 bar:
– Measuring range start ASt2 can be set
between –0.5 and +0.5 bar (  4 mA/0 V).
– Measuring range end AEn2 can be set
between 9 and 10 bar (  20 mA/10 V).
Expanded functions
Menu 5
(Transition to menu level two)
E F
Second menu level
Menu 5/1
Resetting
Resetting all changeable parameters to
r E S
factory defaults and clearing min. and max.
values.
= yes
YES
= no
NO
Menu 5/2
Setting the switch-on delay
and
Setting the value for the switch-on delay
Menu 5/4
after reaching the switch-on point 1 or 2
/
(0.0...50.0 s)
dS 1
dS 2
Menu 5/3
Setting the switch-off delay
and
Setting the value for the switch-off delay
Menu 5/5
after reaching the switch-off point 1 or 2
/
(0.0...50.0 s)
dr 1
dr 2
Menu 5/6
Setting switching outputs 1 and 2
and
Switching function for the switching out-
Menu 5/7
puts:
/
= Hysteresis function, normally open
ou 1
ou 2
Hno
= Hysteresis function, normally closed
Hnc
= Window function, normally open
F no
= Window function, normally closed
F nc
12
english
Display
Second menu level (continued)
Menu 5/8
Changing units
Select physical measuring unit for displayed
uni
and set pressure values:
= bar
bAr
= PSI
PSi
Menu 5/9
Rotate display by 180°
F L I P
Menu
Min. value (display only)
5/10
Display minimum pressure present during
the measurement (value is lost if power is
L o
interrupted)
Menu
Max. value (display only)
5/11
Display maximum pressure present during
the measurement (value is lost if power is
Hi
interrupted)
Menu
Clearing Min. and Max. values
5/12
Execution of the clear values action is
confirmed on the display
À À À À
Menu
Zero point adjustment
5/13
Setting/correcting the zero point of the
display and of the analog output signal by
SE t 0
up to ±3% of the nominal pressure range.
= yes
YE S
= no
NO
Menu
Measurement value damping
5/14
Setting the value for measurement value
damping
dAP
(0...1000 ms in 10 ms increments)
Menu
Access protection
5/15
Setting the password for menu access
protection
c odE
0000 = no password (disabled)
0000...9999 selectable (enabled)
Menu
Output signal 1
5/16
Options:
= PNP
o 1
PnP
= NPN
nPn
Menu
Output signal 2
5/17
Options:
= PNP
o2
PnP
= NPN
nPn
= 4...20 mA current output
i
= 0...10 V voltage output
u
Menu
Displays number of pressure peaks
5/18
Pc nt
Display
= mbar
nnBa
= MPa
NPA