3.4
Description of parameters
PARA-
Description
METER
SP
Setpoint of control
P (%)
Manual mode (%)
ASP1
Alarm setpoint
If ALm1 = 0, 1, 4 or 5 :
alarm setpoint value
If ALm1 = 2, 3, 6, 7, 8, 9, 10 or
11 : bandwidth
If ALm1 = 12 or 13 : timer
rr
Ramp rate for the process value
oFSt
Offset value for manual reset
SHiF
Offset shift for process value
Pb
Proportional band
ti
Integral time
td
Derivative time
LoCL
Local mode
SEL
Parameters selection
(allows selection of additional
parameters to be accessible
at Level 0 security, i.e. without
having to press key for 6 s).
Ct
Proportional cycle time
In
Input mode selection
ALm1
Alarm mode selection
Process alarms are at fixed
temperature points. Deviation
alarms move with the setpoint
value.
Adjustment Range
LLit...HLit
0...100%
LLit...HLit
0...3600 minutes
If 0 ≤ in ≤ 9 : 0...200 °C/min.
If in = 10 : 0...3600 unit/min.
0...100% (« ti » =0)
-111°...111°C
0...200°C
0% (ON-OFF mode)
0...3600 s
0...1000 s
0 : no control parameters can be changed
1 : control parameters can be changed
0 : none
1 : ASP1
2 : rr
3 : oFSt
4 : ASP1, rr
5 : ASP1, oFSt
6 : rr, oFSt
7 : ASP1, rr, oFSt
0...120 s
0 : thermocouple J
1 : thermocouple K
2 : thermocouple T
3 : thermocouple E
4 : thermocouple B
5 : thermocouple R
6 : thermocouple S
7 : thermocouple N
8 : Pt 100 Ω (DIN 43.760)
9 : Pt 100 Ω (JIS C1604-1981)
10 : linear voltage -10...60 mV DC
0 : process high alarm
1 : process low alarm
2 : deviation high alarm
3 : deviation low alarm
4 : inhibit process high alarm
5 : inhibit process low alarm
6 : inhibit deviation high alarm
7 : inhibit deviation low alarm
8 : outband alarm
9 : inband alarm
10 : inhibit outband alarm
11 : inhibit inband alarm
12 : alarm relay On as Dwell Time output
13 : alarm relay Off as Dwell time output
30
Lt settings
200°C
0°C/minute
20.0%
0°C
10°C
120 s
30 s
1
0
Relay output : 20 s
Analogue output : 0 s
Pulsed voltage : 1s
0
1