Adiabatic Panels Adjustment (Adiabatic System And Emeritus®) - LU-VE Emeritus LU1W Manual De Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

PARAMETER
NAME
Wet resources activation delay
PR42
from fans activation
MODBUS Registers
MODBUS
MODBUS
Parameter Name and
Register
Register
Description
Base 0
Base 1
PR42
Wet resources activation
0x07A6
1959
delay from fans activation
4.4
Adiabatic panels are placed on the side of the exchanger at the air inlet; the water that percolates in the panels
evaporates in the air flow and increases relative humidity, thus lowering the temperature due to adiabatic cooling.
During the activation of the adiabatic panels the fan speed is constant and equal to parameter PF35; the water flow
rate is modulated by the adiabatic panels, by means of a modulating valve (AO2) and a flowmeter (AI7), with impact
on the air outlet temperature of the panels.
The controller enables the operation of the adiabatic panels only if the outside temperature is above the set threshold
(parameter PE11, with hysteresis parameter PE13). In addition, the demand for the adiabatic panel resource must be
higher than parameter PR36 % to control the opening of the supply valves and start to spray the adiabatic panels.
PR19
PF35
SP-PR03
The opening of the modulating valve varies according to the required water flow and the water flow measured by the
flowmeter. It is possible to select different algorithms for the control of the adiabatic panels, via parameter PR31;
using these algorithms, starting from a water flow set-point (parameter PR32) set by LU-VE, a required water flow is
defined. Parameters PR33, PR34, PR35 are the additional parameters for flow adjustment; the PR37 and PR38
parameters represent the minimum and maximum opening of the modulating valve (in% on the range 0% = closed -
100% = totally open).
Attention: Changing the PR32 water flow set-point can lead to malfunction and/or impact on the useful life of
adiabatic panels. Only modify this parameter with caution.
LU1W - User Manual
DESCRIPTION
Data Type and Notes
[sec]
- unsigned short int
Adiabatic Panels Adjustment (Adiabatic System and EMERITUS®)
PR04
Adiabatic Panel Adjustment
DEFAULT
MIN
VALUE
VALUE
30
0
Default
value
30
PR32
PR38
PR37
Temp.
SP
43
MAX
UM
VALUE
9999
sec
Decimal
Min
Max
positions
0
9999
IN: water supply line
FL
EV: solenoid valve
EV SC: drain valve
V1: modulating valve
V1
FL: flowmeter
UV lamp (optional)
UV
lamp
EV SC
EV
IN
REV.1.1 – 07/11/2017 - ENG
MENU
ADVANCED →
REGULATION
MODBUS
Register
Type
0
holding

Publicidad

Tabla de contenido
loading

Tabla de contenido