PARAMETER
NAME
PF04
Maximum fan speed in RPM
MODBUS Registers
MODBUS
MODBUS
Parameter Name and
Register
Register
Description
Base 0
Base 1
PF04
0x0C15
3094
Maximum fan speed
* This value assumes the maximum speed allowed by the fan
•
Setting and modifying fan speeds in absence of communication. Because of MODBUS signal loss (due to
controller malfunction or signal cable damage, for example), the fans rotate at the RPM (absolute RPM) set to
parameter PF05.
ATTENTION! If during maintenance, communication with the controller is interrupted while the fans are
powered, the fans rotate at the set speed thereby creating danger to the operator.
ATTENTION! When parameter PF05 is changed, the new value is written in the fan EEPROM. Given the
limited number of write/erase cycles of the fan EEPROM (100,000), you may need to be careful to set this value
via MODBUS; an entry at each cycle of the remote supervisor would lead to an early deterioration of the fan
EEPROM.
PARAMETER
NAME
Fan speed in absence of MODBUS
PF05
communication
MODBUS Registers
MODBUS
MODBUS
Parameter Name and
Register
Register
Description
Base 0
Base 1
PF05
Fan speed in absence of
0x0C16
3095
MODBUS communication
•
Reading states (active, not active, error), speeds and instantaneous absorption of individual fans. The
parameters are displayed on the information screens in VENTILATION and those for the single fan, and are
available to the registers via MODBUS:
LU1W - User Manual
DESCRIPTION
Data Type and Notes
[RPM]
- unsigned short
DESCRIPTION
Data Type and Notes
[RPM]
- unsigned short
DEFAULT
MIN
VALUE
VALUE
6000 *
0
Default
value
6000*
DEFAULT
MIN
VALUE
VALUE
PF04/2
0
Default
value
PF04/2
64
MAX
UM
VALUE
6000*
RPM
Decimal
Min
Max
positions
0
6000*
MAX
UM
VALUE
RPM
PF04
Decimal
Min
Max
positions
0
PF04
REV.1.1 – 07/11/2017 - ENG
MENU
USER →
FUNC. FAN
MODBUS
Register
Type
0
holding
MENU
USER →
FUNC. FAN
MODBUS
Register
Type
0
holding