10.1 Spray and Adiabatic Panel Hours Control
For each spray sector and for the adiabatic panels present on each side of the exchanger, the total operating hours
and annual operating hours are stored. Each year the annual operating hours are automatically reset; the reset date is
given by PH96 and PH97.
If the annual operating hours of the sprayers and adiabatic panels exceed the set thresholds, parameter PA04 for
sprays and parameter PA05 for adiabatic panels, the controller gives a warning alarm.
For the spray sector only, the resource is blocked from exceeding an additional 10% above the set threshold (i.e. block
occurs when the annual hourly total reaches PA04 * 1.1).
PARAMETER
NAME
READ ONLY
PA04
Spray annual operating hours limit
READ ONLY
PA05
Adiabatic panels annual operating
hours limit
READ ONLY
Day when to reset spray and
PH96
adiabatic panels annual operating
hours
READ ONLY
Month in which to reset spray and
PH97
adiabatic panels annual operating
hours
MODBUS Registers
MODBUS
MODBUS
Name and Description
Register
Register
Parameter
Base 0
Base 1
PA04 (Low)
Spray annual operating
0x07F9
2042
hours limit
0x07FA
2043
PA04 (High)
PA05 (Low)
Adiabatic panels annual
0x07FB
2044
operating hours limit
0x07FC
2045
PA05 (High)
PH96
Day when to reset spray
and adiabatic panels
0x082C
2093
annual operating hours
PH97
Month in which to reset
spray and adiabatic
panels annual operating
0x082D
2094
hours
LU1W - User Manual
DESCRIPTION
Data Type and Notes
[hours]
- long int divided into 2
word 16 bit
[hours]
- long int divided into 2
word 16 bit
- unsigned short int
1 = January, 2 =
February, .. , 12 =
December
- unsigned short int
DEFAULT
MIN
VALUE
VALUE
500
0
2000
0
1
1
January
January
December
Default
value
500
2000
1
1
92
MAX
UM
VALUE
hours
1000
5000
hours
-
31
-
Decimal
min
Max
positions
0
1000
0
1000000
1
31
1
12
REV.1.1 – 07/11/2017 - ENG