MODBUS Registers
MODBUS
MODBUS
Name and Description
Register
Register
Parameter
Base 0
Base 1
PA00
0x07F6
2039
Reset alarms at power on
PA01
0x07F7
2040
Probe error report delay
PF23
0x07B9
1978
Fans speed in probe error
PE14
Enables wet resources
adjustment with outdoor
0x07DD
2014
temp. probe error
LU1W - User Manual
Default
Data Type and Notes
value
0 = disabled,
1 = enabled
- unsigned short int
[sec]
- unsigned short int
[%]
- unsigned short int
100.00
0 = disabled,
1 = enabled
- unsigned short int
104
Min
Max
1
0
1
8
1
255
0.00
100.00
1
0
1
REV.1.1 – 07/11/2017 - ENG
MODBUS
Decimal
Register
positions
Type
0
holding
0
holding
0.00
holding
0
holding