SPECIFICATIONS
Rated Maximum Power (LP*) . . . . . . . . . . . . . . . . . .7.0 kW
Rated Maximum Load Current:
at 240 Volts . . . . . . . . . . . . . . . . . . . . . . . . . . . .29.1 Amps
at 120 Volts . . . . . . . . . . . . . . . . . . . . . . . . . . . .58.2 Amps
Rated AC Voltage . . . . . . . . . . . . . . . . . . . . . . .120/240 Volts
Rated Frequency . . . . . . . . . . . . . . . . . .60 Hz at 3600 rpm
Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Single Phase
Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.0
NG Fuel Supply Pressure . . . . . . . . . . . . . . . . . .5-7 in W.C.
LP Fuel Supply Pressure . . . . . . . . . . . . . . . . .11-14 in W.C.
Normal Operating Range -20°F (-28.8°C) to 104°F (40°C)
Output Sound Level . . .81 dB(A) at 23 ft. (7 m) at full load
Shipping Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . .280 lbs.
* Natural gas rating will depend on specific fuel but typical
derating of generator is between 10 to 20% off the LP gas
rating.
More user manuals on
Briggs & Stratton Power Products Home Standby Generator
Installation, Start-Up and Owner's Manual
ManualsBase.com
SYSTEM OPERATION
To select system operation, do the following:
1.
Push and hold START/RUN/STOP switch in START
position until LED comes on.
2.
Refer to the transfer switch manual for proper transfer
from utility to generator.
Servicing the Generator
To service generator:
1.
Remove roof by removing four screws and lifting off.
2.
Remove screw at top of control panel access door.
3.
Pull access door outward (away) from unit while
pulling door upward and out of base. Door will come
free of generator enclosure.
4.
Pull service disconnect from disconnect box.
5.
Set generator's main circuit breaker to OFF position.
6.
Remove 15A fuse from control panel.
19