●When "Holiday mode" has been activated, the controller will automatically deactivate the "Weekly timer" and
"Preset mode"and "Clock timer" and "Temp.timer".
●Under the "Holiday mode", when the unit is under the control of room temperature, the set point (room
temperature for heating) should be set to 10°C; when it is under the control of leaving water temperature, the set
point (leaving water temperature for heating) should be 30°C.
● When this function has been activated, "Floor debug", "Emergen.mode", "Disinfection", "Manual defrost",
"Preset mode", "Weekly timer", "Clock timer", and "Temp.timer" cannot be activated at the same time,
meanwhile a window will pop up, saying "Please disable the holiday mode!".
●This function will be memorized upon power failure.

2.2.14 Preset Mode

[Operation Instructions]
At the function setting page, select "Preset mode" and go to the corresponding setting page.
At the time period setting page, each time period can be set to "Valid" or "Invalid".
The option "Mode" is used to preset the mode; "WOT-Heat" is used to set the leaving cold/hot water
temperature; "Start timer" / "End timer" is used to for time setting. After that, by touching the "Save" icon, all
settings will be saved.
[Notes]
● When "Preset mode" has been set to "Hot water" and "Water tank" is to set to "Without", the preset "Hot
water" mode will be automatically switched to "Heat".
● When "Weekly timer" and "Preset mode" both have been set, priority will be given to the latter.
● When the water tank is available, the preset mode can be "Heat", "Cool", or "Hot water"; however, when the
water tank is unavailable, the preset mode can only be "Heat" or "Cool".
● "Start timer" should be earlier than "End timer", otherwise a dialog will pop up, saying "time setting wrong".
● The setting for "Preset mode" will works until it has been canceled manually.
● When "Start timer" is reached, the unit will perform the preset mode. In this case, mode and temperature
setting are still allowed but will not be saved to the preset mode. When "End timer" is reached, the unit will
perform OFF operation.
●This function will be memorized upon power failure.