salmson SIE Serie Instrucciones De Instalación Y Funcionamiento página 63

Ocultar thumbs Ver también para SIE Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Terminal
Fig. 20: Control terminals
Fig. 21: Mains connection terminals
Installation and operating instructions SIE - DIE
• The connection line is to be placed in such a way that it can under no
circumstances come into contact with the pipe and/or the pump and
motor housing.
• This pump is equipped with a frequency converter and may not be
protected by a residual-current-operated protection switch. Fre-
quency converters can impair the function of residual-current-oper-
ated protection circuits.
Exception: residual-current-operated protection switches which
have a selective universal-current-sensitive design are allowed.
• Labelling: RCD
• Trigger current: > 30 mA
• Check the current type and voltage of the mains connection.
• Observe the type plate information for the pump. The current type
and voltage of the mains connection must correspond to the specifi-
cations on the name plate.
• Mains side fuse protection: max. permissible 25 A
NOTE
Trigger characteristic of the fuses: B
• Control terminal (Fig. 20)
(See following table for allocation)
• Mains connection terminals (Fig. 21)
(See following table for allocation)
English
57

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Die serie

Tabla de contenido