English
11.3.2 Error type B
5
8
Fig. 44: Error type B, diagram
Incidence X < Y
6.0.0.0
E000
6.0.0.0
3/6
Fig. 45: Acknowledge error type B (X < Y)
Incidence X = Y
6.0.0.0
E000
6.0.0.0
300
6/6
6.0.0.0
6/6
Fig. 46: Acknowledge error type B (X = Y)
82
1
2
3
4
6
9
7
75
12.3
S
S
0
12.3
S
Error type B (Fig. 44):
Program
Contents
step/query
1
• Error code is displayed
• Motor off
• Red LED on
2
• Error meter is increased
3
Error meter > 5?
4
• SSM is activated
5
> 5 minutes?
6
> 5 minutes?
7
Error acknowledged?
8
End; auto control is continued
9
Error E021 > 1 minute
Yes
No
If type B errors occur, proceed as follows to acknowledge:
• To change to the menu mode, press the acknowledge button.
The menu number <6.0.0.0> flashes.
• Press the acknowledge button again.
The menu number <6.0.0.0> is displayed statically.
On the units display, the current incidence (x) as well as the maximum
incidence of the error (y) are displayed in the format "x/y".
If the current incidence of the error is less than the maximum inci-
dence (Fig. 45):
• Wait till the auto reset time is over.
On the value display, the remaining time till auto reset of the error is
displayed in seconds.
After the auto reset time has run out, the error will be automatically
acknowledged and the status page will be displayed.
NOTE
The auto reset time can be set at menu number <5.6.3.0> (time input
10 to 300 s)
If the current incidence of the error is the same as maximum incidence
(Fig. 46):
• Wait until the remaining time is up.
The time till manual acknowledgement is always 300 seconds.
On the value display, the remaining time till manual acknowledge-
ment of the error is displayed in seconds.
• Press the acknowledge button again.
The error is acknowledged and the status page is displayed.