Analog ouput channel
Rapid current limit
Monopulse control
Fixed length control
Timing control
Virtual terminal
Keypad display
Lock the button
Use ambient
Altitude
Environment temperature -10ºC~+40ºC (environment temperature between 40ºC~50ºC,
Environment humidity
Vibration
Storage temperature
130
Channel 2 for analog signal output, AO1 can choose 4~20mA
or 0~10V, AO2 can choose 4~20mA or 0~10Vto achieve setting
frequency, output frequency and other physical quantity output,
which can be expanded to channel 4 analog output.
Limit inverter over current to the greatest point, and make it run
more stably
Suitable for working site where need one button to control
inverter start and stop, first press to start, then press to stop,
and that cycle repeats. Its very simple and reliable.
Realize fixed length control
Timing control function: setting time range 0.1Min ~ 6500.0Min
Five group virtual input & output IO can realize simply logical
control
The parameters like setting frequency, output frequency, output
voltage, output current can be displayed
Lock all or part of the buttons
Motor power on Shot circuit test,
input & output phase loss protection,
over-current protection,
over voltage protection,
under voltage protection,
over heat protection,
overload protection,
under load protection,
relay absorption protection,
terminal protection and no stop protection under power off.
Indoor, not bare to sunlight, no dust, no corrosive gas, no
flammable gas, no vapor, no water drop or salt etc.
Under 1000 meter. (above 1000 meter require to reduce volume
to use, output current reduce about 10% of rated currenvolt per
1000 meter
high)
need to reduce volume or strengthen heat sink )
Smaller than 95%RH, no drop condenses
Smaller than 5.9 M/S²(0.6g)
-40ºC~+70ºC