No.
Function
Input and output control
CN3
of external terminal
CN4
Signal output of relay
Crystal RS485
CN6
communication interface
No.
Function
AI1 Analog input signal
SW1
selection
AI2 Analog input signal
SW2
selection
AO1 Analog output signal
SW3
selection
AO2 Analog output signal
SW4
selection
EMI inhibition for selection
SW5
terminal
Table 3-4 Descripción de la función de switch para los usuarios
01.
In the graphic of slide switch, black square means switch slidable
location.
02.
Only when heavy interfering exist on working site it's suggested to
put EMI dial switch to earth grounding location, and should connect
to the earth.
To use when inverter run under external terminal control, refer
to 3.6.2
TA-TC is normal open contact; TB-TC is normal closed
contact, refer to 3.6.2
To use when inverter through 485 communication can
achieve cascade connection and other control, refer to 3.6.2
Table 3-3 Función de los terminales
V: F00.20 be XXX0
0~+10V voltage signal input
I: F00.20 be XXX1
4~20mA current signal input
V: F00.20 be XX0X,
-10V~+10V voltage signal input
I: F00.20 be XX1X,
4~20mA current signal input
V: F00.21 be XX00
0~+10V voltage signal output
I: F00.21 be XX11
4~20mA current signal output
: earth grounding
: suspending
3. Installation and wiring
Description
Setting
Default value
F00.20 be 0000
0~+10V
F00.20 be 0000
-10V~+10V
F00.21 be 0000
0~+10V
suspending
141