F19.27
Feedback lost detection
value
F19.28
Feedback lost
detection time
F19.29
Deviation magnitude
abnormal detection
value
F19.30
Deviation magnitude
abnormal detection
time
F19.31
Protection action
selection 1
F19.32
Protection action
selection 2
F19.33
Reserved
F19.34
Reserved
F19.35
Fault indication and
clock during the period
of recovery
202
0~100%
0.0~6000.0s
0~100%
0.0~6000.0s
. units digit: PID provide loss detection act
0:no detection
1:alarm, continue run
2:alarm, stop run as halt mode
3:fault, free halt
. tens digit: PID feedback loss detection act
0:no detection
1:alarm, continue run
2:alarm, stop run as halt mode
3:fault, free halt
. hundreds digit: PID error value abnormal
detect action
0:no detection
1:alarm, continue run
2:alarm, stop run as halt mode
3:fault, free halt
. units digit: communication abnormal
action: include communication time out
and error
0:alarm, continue run
1:alarm, stop run as halt mode
2:fault, free halt
. tens digit: E
PROM abnormal action
2
selection
0:alarm, continue run
1:alarm, stop run as halt mode
2:fault, free halt
. hundreds digit: contactor abnormal action
0:alarm, continue run
1:alarm, stop run as halt mode
2:fault, free halt
.thousands digit: undervoltage fault
indication action selection
0:no detection
1:fault, free halt
. units digit: fault indication selection during
the period of fault reset automatically
0:action
1:no action
. tens digit: fault clock function selection: to
achieve fault display before power down: etc.
0:forbid
1:open
1%
12%
o
0.1s
0.5s
o
1%
50%
o
0.1s
0.5s
o
1
000
o
1
1200
×
1
00
×