E-10
Motor overload
(A-10)
protection
E-11
Motor underload
(A-11)
protection
The input phase
E-12
lose
The output
E-13
phase lose
Inverting module
E-14
protection
Motor overload protection
Power source voltage is too low
General motor run at low
speed with big load
Motor overload protection factor set
incorrectly
Motor blocked up or load change
too suddenly and quickly
The operating current of inverter
less than underload threshold
load divorced from motor
The three-phase input power supply
is abnormal
Power supply board anomaly
The control board anomaly
When the motor runs inverter three-
phase output
unbalanced
When the motor runs inverter three-
phase output
unbalanced
Power supply board anomaly
The control board anomaly
Transient overcurrent of the inverter
phase to phase short circuit or
earthing short circuit of output 3
phase
Air-path blocked or fan damaged
Ambient temperature is too high
7. Troubleshooting
Adjust V/F curve and torque boost
check power source voltage
Can choose frequency conversion
motor for long time low speed run
to set motor overload protection
factor correctly
Check the load
Confirm whether the parameters F19.08,
F19.09 setting are reasonable
Checking whether the load divorced from
motor
Check the three-phase input power line is
off or poor contact
Look for service from manufacturer or
agent
Look for service from manufacturer or
agent
Check whether the motor
three-phase winding is balance
Check whether the motor
three-phase winding is balance
Look for service from manufacturer or
agent
Look for service from manufacturer or
agent
Refer to countermeasure for
overcurrent
wiring again
To clear air-path or replace the fan
Lower ambient temperature
213