NOTE: Never allow the drain hose to hang or loop higher than the floor of the ice
storage bin.
2. All horizontal runs of drain lines must have a fall of ¼" per foot. An air gap will likely
be required between the ice maker drain tube and the drain/waste receptacle. A
standpipe with a trap below it would be acceptable for the drain/waste receptacle. A
floor drain is also acceptable. If this is not possible,
the use of a condensate pump. Contact
- 316 - 1725.
3. Pour 1 gallon of water into the ice storage bin to check for leaks in the drainage system.
Tighten any connections that leak.
IMPORTANT: This ice maker is not a freezer. Infrequent drainage will
cause a high rate of melting in the ice storage bin.