AVENTICS | DeviceNet | R402003659–BAL–001–AG
Commissioning and operation
S3
ON
OFF
S1
S2
7.1.1

Setting the data rate

O
Set the data rate (baud rate) with the DIP-switch S3.1 to S3.3 in
accordance with the information listed in Table 8 below.
Default setting: 125 kbit/s
Table 8
S3, switch assignment for data rate setting
Data rate
Max. wire length
Reserved
Reserved
Reserved
Reserved
Reserved
500 kbit/s
100 m
250 kbit/s
250 m
1)
125 kbit/s
500 m
1)
Default setting
7.1.2

Setting the bus coupler address

To identify each individual bus coupler correctly a unique station
address must be set using switches S1 and S2.
Changes during operation
Changes to the addressing are only activated after a power reset.
O
Never change the settings during operation.
O
Turn the device off before changing the address setting.
O
Assign the station address freely from 0 to 63 (maximum MAC ID
is 63) using S1 and S2.
– S1: Unit digits from 0 to 9
– S2: Tens digits from 0 to 9
– [S2] [S1] = Station address
Default setting: MAC ID = 63