Chauvin Arnoux STATOP 4850 Manual De Instrucciones página 27

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Level
Index
Parameter
XXXX
Process value
YYYY
Setpoint value
ASP1
Setpoint of absolute alarm (if A1.md = FS.hi or FS.Lo )
Setpoint of following alarm (if A1.md ≠ FS.hi or FS.Lo )
Timer (if A1.SF = to.on or to.oF )
rAmP
Ramp of temperature rise
oFSt
Manual offset of proportional band
ASP2
Setpoint of absolute alarm (if A2.md = FS.hi or FS.Lo )
Setpoint of following alarm (if A2.md ≠ FS.hi or FS.Lo )
ShiF
Display offset
Pb
Proportional band channel 1 (hot)
ti
Integral time
td
Derivative time
AhY1
Hysteresis of relay of alarm A1
AhY2
Hysteresis of relay of alarm A2
hYSt
Hysteresis on ON-OFF control
Addr
Digital address of the controller
Lo.SC
Lowest limit of scale
hi.SC
Top limit of scale
PL.1
Power limit on channel 1 (hot)
PL.2
Power limit on channel 2 (cold)
inPt
Type of input
unit
Unit of display
rESo
Resolution of display
Con.A
Direction of control channel 1 (hot)
A1.md
Behaviour of alarm A1
A1.SF
Special functions for alarm A1
A2.md
Behaviour of alarm A2
A2.SF
Special functions for alarm A2
CYC
Channel 1 modulation cycle (hot)
C.CYC
Channel 2 modulation cycle (cold)
C.Pb
Channel 2 proportional band (cold)
d-b
Dead band (band offset C.Pb/Pb)
Adjustment range or possible choice
Lo.SC...hi.SC
Lo.SC...hi.SC
-111,0...+111,0°C
0...9999 minutes
0...55,55°C/minute
0...100% ( ti must equal 0)
Lo.SC...hi.SC
-111,0...+111,0°C
-111,0...+111,0°C
0...+200,0°C (0 = ON-OFF action)
0...3600 seconds
0...1000 seconds
0...+11,0°C
0...+11,0°C
0...+11,0°C
0...40
see text
see text
0...100%
0...100%
J-tC
J couple
k-tC
K couple
t-tC
T couple
E-tC
E couple
b-tC
B couple
r-tC
R couple
S-tC
S couple
n-tC
N couple
Pt.dn
Pt 100 DIN
Pt.JS
Pt 100 JIS
4-20
4...20 mA
0-20
0...20 mA
0-1v
0...1 V
0-5v
0...5 V
1-5v
1...5 V
0-10
0...10 V
°C
degree centigrade
°F
degree Fahrenheit
p.u
other (V or mA)
no.dP
no decimal
1.dP
1 decimal
2.dP
2 decimals
dirt
direct
rEvr
reverse
dv.hi
high gap
dv.Lo
low gap
db.hi
high symmetrical
db.Lo
low symmetrical
FS.hi
high absolute
FS.Lo
low absolute
nonE
none
Lt.Ch
locking state
hoLd
prohibit 1st fault
Lt.ho
Lt.Ch + hoLd
to.on
timer
to.oF
timer
idem parameter A1.md
nonE
none
Lt.Ch
locking state
hoLd
prohibit 1st fault
Lt.ho
Lt.Ch + hoLd
Cool
proportional control output 2 (cold)
0...99 seconds
0...99 seconds
0,0...+200,0°C
-111,0...+111,0°C
27
Preset
value
+100,0°C
+10,0°C
0,00°C/min
0,0%
+10,0°C
0,0°C
+10,0°C
120 s
40 s
0,0°C
0,0°C
0,0°C
0
-17,7°C
+537,7°C
100%
100%
K couple
°C
1 decimal
reverse
high gap
none
high gap
none
20 s
20 s
+10,0°C
0,0°C