On-Off Control; Hot-Cold Control; Ramp And Dwell Functions - Chauvin Arnoux STATOP 4850 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3.9. ON-OFF CONTROL

Introduce a nil proportional band ( Pb = 0). The output control
becomes an ON-OFF output, with adjustable hysteresis (parameter
hYSt ) :
ON-OFF control can generate excessive fluctuations if the hysteresis
is too low.
In ON-OFF mode, the parameters ti , td et CYC no longer have
an effect. Likewise, manual mode and autotune are no longer
accessible.

3.10. HOT-COLD CONTROL

Output configuration
Cold ON-OFF (no hot)
Proportional cold (no hot)
Hot + Cold ON-OFF
Proportional Hot + Cold
Function of C.Pb and d-b : The cold proportional band C.Pb and the dead band d-b are measured in degrees.

3.11. RAMP AND DWELL FUNCTIONS

By default, the controller is configured so as to reach the setpoint as directly as possible. By introducing a ramp, you oblige the
controller to rise to the setpoint in a gradual way, more or less rapidly depending on the slope of this ramp. It is what is also called
the SOFT START function.
In addition, alarm A1 can be configured as a Timer, and this timer can be combined with the Ramp function. This guarantees a
constant temperature during a given time.
3.11.1. Ramp (SOFT START)
To activate the Ramp function, simply introduce a non-zero slope for the rAmP parameter. When rAmP has a value of zero, the
Ramp function is inhibited.
Hot output
Cold output
No
OUT1
No
OUT1
OUT1
A2
OUT1
A2
Cold ouput
100%
DB
negative
0%
SV
SV + DB
34
PV
SV + HYST/2
SV
SV - HYST/2
Ouput 1
Reverse action
100%
0%
Con.A = rEvr
Direct action
100%
Con.A = dirt
0%
Adjustment of parameters
Con.A = dirt
Pb = 0
hYSt
Setpoint
Con.A = dirt
Pb , ti , td , CYC , Setpoint
Con.A = rEvr
A2.SF = nonE
A2.md = dv.hi (or FS.hi )
AhY2 , Setpoint (or ASP2 )
Con.A = rEvr
A2.SF = CooL
C.Pb , d-b , C.CYC , Setpoint
DB
Positive
PV (°C or °F)
CPB
Time
Time