Temperature blocking:
In order to lock the set temperature, insert pegs on both sides of the "stop rib".
Temperature setting:
The factory setting of the thermostat is arranged so that the number 3 on the graduated scale gap
corresponds to a room temperature of 20°C.
Should this setting be inadvertently disturbed, the following procedure should be undertaken in
order to restore it:
– First remove the frame cover and pull-off the graduated scale cap.
– Turn the centre adjustment screw clockwise until stop, and then turn it anticlockwise until the
factory red paint marks falls in line with the "stop rib".
– Then replace the graduated scale cap so that the number 3 also falls in line with the "stop rib".
– Thus the original setting is restored.
– Finally replace the gram cover (Illustration 6).
Illustration 6
Thermostat setting
0 = valve shut off
=
Frost protection. With this setting,
TRW open automatically when the room
temperature falls below 7ºC
1 = approx. 12°C
2 = approx. 16°C
3 = approx. 20°C
4 = approx. 24°C
5 = approx. 28°C
Intermediate positions
between numbers 2 and
4 correspond to a 1ºC
change in the room
temperature