Módulos De Múltiples Circuitos Anunciadores Para Anunciación De Zonas - DMP XR200 Guia De Instalacion

Tabla de contenido

Publicidad

25.3 Módulos de múltiples circuitos anunciadores para anunciación de zonas
To additional Zone 1 Notification Circuit
Modules.
Install up to a maximum of twenty-five
866 Modules by using the relay outputs
available on the XR200 panel.
All modules must be installed in a
340FC, 349, or 350 Enclosure connected
by no more than 20 feet of conduit.
Zone 1 Notification
Circuit Module
DMP Model 866
45mA @ 12 VDC
Normal/Silence Switch
866 Module
1 AUX PWR
S
2 GND
S
3 Alarm In
S
4 Bell PWR In
S
S
5 Bell Out +
6 Bell Out -
S
S
7 Bell Trouble
1K EOL
8 Bell Trouble
S
+ -
24 VDC
504-24
5 Amp
Power
Maximum
Supply
Power Supply Trouble
Contacts N/C
24 VDC
504-24
5 Amp
Power
Maximum
Supply
+ -
Normal/Silence Switch
865 Module
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In +
5 Bell PWR In -
6 Bell Out A +
7 Bell Out A -
8 Bell Out B +
9 Bell Out B -
S
10 Bell Trouble
S
11 Bell Trouble
Zone 2 Notification
Circuit Module
To additional notification
DMP Model 865
circuit modules.
26mA @ 12 VDC
XR200 Guía de Instalación
DIAGRAMAS DEL SISTEMA
J12
J11
J3
DD, MPX
Selection
Headers
Answering Machine
Ground Start Relay
Bypass Relay
K2 K4
Use Model 305
Use Model 305
AC
AC
+B
-B
BELL GND
RED YEL GRN BLK
1
2
3
4
5
6
7
S
S
S
S = Supervised Circuit
10K EOL
DMP Model 308
UL Listed,
Polarized
Style W
Notification
Appliances
Each 866 Notification Appliance
Circuit Module in alarm draws up to
30mA through its Terminal 3 Alarm
Input and 45mA from its Terminal 1
Aux Power Input.
S
S
S
S
Each 865 Notification Appliance
Circuit Module in alarm draws up to
59mA through its Terminal 3 Alarm
Input and 26mA from its Terminal 1
Aux Power Input.
XR200 Command Processor™ Panel
J4
Tamper
Header
J2 Output Header
All outputs must be located
within the same room as
the control panel.
J10
Relay Output 1
Relay Output 2
K6 K7
Use Model 305
Use Model 305
SMK GND
Z1
GND
Z2
Z3
GND
Z4
8
9
10
11
12
13
14
15
16
17
18
S
S
S
S
Common Notification
Circuit Module
DMP Model 866
45mA @ 12 VDC
Normal/Silence Switch
866 Module
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
+ -
24 VDC 5
504-24
Amp
Power
Maximum
Supply
1K EOL
Power Supply Trouble
Contacts N/C
+
-
UL Listed,
Polarized
Style y
Notification
+
Appliances
-
J16
Panel
Reset
Z5
GND
Z6
Z7
GND
Z8 Z9+ Z9- Z10+ Z10-
19
20
21
22
23
24
25
26
27
28
Outputs 3 through 10
can switch up to
Zone 1 Output
50mA each at 12
Relay 1
N/O
VDC. This is
Orange
sufficient for one 866
Zone 2 Output
Module per indicating
Relay 1
zone 3 through 10.
N/O
Orange
Relay 1 and 2
Common
Gray
10K EOL
DMP Model 308
Style W
UL Listed,
Polarized
Notification
Appliances
Auxiliary Power Supply must be
regulated, UL Listed for Fire Protective
Signaling Service. Power Supplies must
have battery backup.
The Auxiliary Power Supply and
Notification Circuit Module trouble
contact zone must be programmed as
a Supervisory Type zone and must be
selected for display in the keypad
status list (See section 10.6 in the
Programming Guide (LT-0196)).
Note: If an auxiliary power supply is
not used, terminals 3 and 4 can be
jumpered together to supply Bell
Power from the XR200 panel.
A maximum of 1.5 Amps as 12 VDC is
available from terminal 5 of the
XR200 panel.
Digital Monitoring Products
27

Publicidad

Tabla de contenido
loading

Tabla de contenido