Electrical installation

8
Electrical installation
Screw terminal data
Terminal X301
Mains filter
E94AZMS0034
E94AZMS0094
E94AZMS0184
E94AZMS0314
There is an M5 connection screw for the PE conductor.
Installation steps
K1
L1
L2
L3
N
PE
How to connect the filter:
1. Connect filter output cable (X302) to terminal X100 at the mounting base.
2. Connect mains cable to terminal X301.
3. Attach PE conductor to PE screw using fork-type or ring cable lug.
– The PE connection must comply with EN 50178.
– Tightening torque 3.0 Nm (26.5 lb-in).
30
Connection cross-sections
2
[mm
]
2.5
4
10
F1...F3
L1
L2
L3
PE
X301
E94AZxSxxxx
[AWG]
[Nm]
14
0.5 ... 0.6
12
0.5 ... 0.6
8
1.2 ... 1.5
1 (BK)
2 (BK)
3 (BK)
PE (GN/YE)
L1
L2
X302
X100
E94AZPxxxxx
Tightening torque
[lb-in]
4.42 ... 5.31
4.42 ... 5.31
10.6 ... 13.3
L3
PE
SSP94NF007
EDK94AZMS DE/EN/FR/ES/IT 2.1