Product components (Fig� 3�3)
A Load module, power supply lead, surface-mounted
B Load module, power supply lead, concealed
C Designer trim, round or square
D Sensor module
E Shroud

Product dimensions

Surface-mounted / concealed (Fig� 3�4) IS 3360 LiveLink, IS 3360 MX LiveLink,
IS 345 LiveLink
Surface-mounted / concealed (Fig� 3�5) IS 345 MX LiveLink
Surface-mounted / wall-mounted (Fig� 3�6) IS 3180 LiveLink
4� Electrical installation
The mounting location should be at least 50 cm away from other lights because heat
radiated from these may activate the system. An optional corner wall mount (product
no. 648015 black or 035174 white) is available for mounting the IS 3180 LiveLink.
For wiring up the motion detector, the following applies: Under section 6 of
VDE 0100 520, a multiple-core lead containing both the mains voltage leads and
the control leads (e.g. NYM 5 × 1.5) may be used for the wiring between sensor and
LiveLink Box. The lead between LiveLink Box and sensor must be no longer than
300 m (for 1.5 mm²). After installing and switching on, the LiveLink Box takes approx.
45 seconds to start. The sensor then starts to flash once per second during the
initialisation cycle.
If the rubber seal is damaged, the cable entry openings must be sealed with an M16
or M20 (at least IP54) double seal cable gland.
Wiring example (Fig� 4�1)
5� Mounting
• Check all components for damage.
• Do not use the product if it is damaged.
• Select an appropriate mounting location, taking the reach and motion detection
into consideration.
26
Procedure for installing concealed power supply lead (Fig� 5�1)
Procedure for installing surface-mounted power supply lead (Fig� 5�2)
IS 3360 LiveLink, IS 3360 MX Highbay LiveLink, IS 345 LiveLink, IS 345 Highbay
LiveLink
Procedure for installing concealed power supply lead (wall mounting) IS 3180 LiveLink
(Fig� 5�3)
For mounting the IS 3180 LiveLink on the wall, a water drainage hole (Ø 5 mm drill bit)
is marked next to the rubber seal. This must be opened if necessary. (Fig� 5�3)
• Switch OFF power supply� (Fig� 5�1)
• Detach designer trim from sensor module.
• Disconnect sensor module from the load module.
• Connect to mains power supply.
– Surface-mounted power supply lead (Fig� 5�4)
– Concealed power supply lead (Fig� 5�5)
• Insert fastening screws and mount load module.
Detection zone / reach
IS 3360 LiveLink (Fig� 5�6)
IS 3360 MX LiveLink (Fig� 5�7)
Mounting height
Reach
14 m
10 m
9 m
14 m
6 m
16 m
2.8 m
18 m
IS 345 LiveLink (Fig� 5�8)
IS 345 MX LiveLink (Fig� 5�9)
Mounting height
Reach
14 m
30 m × 4
10 m
25 m × 4
8 m
20 m × 4
6 m
15 m × 4
4 m
10 m × 4
27