13.2.2) PROGRAMMING NOTES

Simultaneously pressing <+> and <-> from inside a function menu allows you to return to the previous menu without making any changes. Hold down
the <+> key or the <-> key to accelerate the increase/decrease of the values.
Hold down the <+> key or the <-> key to accelerate the increase/decrease of the values.
After waiting 120s the control unit quits programming mode and switches off the display.
When the board is switched on, the software version is displayed for around 5 sec
The pre-set logic functions and parameters are made taking account of a typical installation.

13.3) PARAMETERS, LOGICS AND SPECIAL FUNCTIONS

The following tables describe the functions available on the control unit
MENU
Select the length of the boom installed on the barrier.
Value expressed in meter from 3m to 5m (EVA5) or from 7m to 8m (EVA7)
BOOM
According to the selected boom length, the optimal value of speed will be set.
* For booms greater than 5 m use the value (7-8)
Set the closing direction of the barrier (see fig. 2)
The symbol 0--- indicates right barrier (R/RIGHT) DEFAULT
Pos
The symbol ---0 indicates left barrier (L/LEFT)
Verify the opening direction of the boom and in case reverse it. Every change of this func-
tion automatically implies the starting of a new AUTOSET procedure.
MENU
Automatic closing time. Enabled only with logic "TCA"=ON.
TCA
At the end of the set time, the control unit commands a closing maneuver .
FSTS
Adjusts the opening and closing speed of the barrier (standard speed, before the slowdown phase).
sldo
Adjusts the slowdown speed of the barrier during the opening phase* (Fig.11 -slow Open).
sldc
Adjusts the slowdown speed of the barrier during the closing phase * (Fig.12 -slow Close).
Sets the starting point of the slowdown during the opening phase (Fig.11- beginning of the slow
tsmo
Open). The value is expressed in percentage on the entire stroke.
Sets the starting point of the slowdown during the closing phase (Fig.12- beginning of the slow
tsmc
Close). The value is expressed in percentage on the entire stroke.
PMO
Adjusts the motor torque applied to the barrier during the opening phase.*
PMC
Adjusts the motor torque applied to the barrier during the closing phase.*
PSO
Adjusts the motor torque applied to the barrier during the slowdown in opening phase * (Fig.10 - Slow Open).
PSC
Adjusts the motor torque applied to the barrier during the slowdown in closing phase * (Fig.11 - Slow Close).
Adjusts the intervention threshold of the anti crushing device (Encoder) during the normal speed*.
SeaU
0:Off -1: minimum sensitivity - 99: maximum sensitivity
Adjusts the intervention threshold of the anti crushing device (Encoder) during the slowdown speed*.
SEAR
0:Off -1: minimum sensitivity - 99: maximum sensitivity
Activation time of the courtesy light contact. Value expressed in seconds. At the beginning of
tls
each maneuver the contact latches for the set time.
See the description of AUX1 parameter.
Sets a short reversion after reaching the limit switch in open position. Can be useful for facilitat-
saso
ing the manual release.
Sets a short reversion after reaching the limit switch in close position. Can be useful for facilitat-
sasc
ing the manual release.
Selects the functioning mode of the auxiliary output 1 (N.O. clean contact)
0: Open barrier light, close contact when the barrier is open, open contact when the barrier is
close, intermittent during the maneuver (fig. 14, SCA)
1: Second radio cannel of the built in receiver
2: Boom light, for controlling the LED light installed on the BOOM (EVA.LED), see also the pa-
aux1
rameter LBAR.
3: Courtesy light, the contact remains close according to the parameter TLS (fig.14 SERVICE LIGHT)
4: Photocells test, see wiring diagram in Fig.14 (PHOTOTEST)
5: Close contact with open barrier
6: Close contact with close barrier
* ATTENTION: A WRONG SETTING OF THESE PARAMETERS CAN BE DANGEROUS.
RESPECT THE REGULATION IN FORCE!

13.3.1) INSTALLATION (INST)

FUNCTION

13.3.2) PARAMETERS (PAR)

FUNCTION
MIN-MAX-(Default)
MEMO
3/5 -7/8 (7-8*)
= RIGHT
0---
= LEFT
---0
( RIGHT )
MIN-MAX-(Default)
MEMO
1-240-(20s)
50-99-(99)
20-70-(50)
20-70-(50)
1-99-(20)
1-99-(20)
1-99-(20)
1-99-(20)
1-99-(20)
1-99-(20)
0-99-(0%)
0-99-(0%)
1-240 (60)
0-5 (0)
0-5 (0)
0-6-(0)