2 | ACCESSORIES
1.
ACCESSORIES
NAME
Adaptor
Cone shoets
QTY
SHAPE
2
2
2
Φ6.4-
Φ12.7-
use for
Dimensions
Φ9.5
Φ15.9
sealing
2.
DIMENSIONS
65 65 65
Φ15.9
Φ9.5
303
343
265
410
3.
PIPEWORK LENGTHS
Outdoor unit
L1
L2
A
B
Fig.2
Total Pipe Length (Actual)
Maximum Piping (L)
Pipe Length (from 's' box to indoor unit
pipe)
Indoor Unit-
Outdoor Unit Up
Outdoor
Outdoor Unit Down
Unit Drop Height
Indoor Unit to Indoor Unit Drop Height
• Model limitation: Indoor unit capacity≤7100W
• The mini branch box should be placed between the indoor and
outdoor units.
6720862459 (16/04)
Installation
Brass nut
manual
This manual
2
2
2
use for
Φ9.5
Φ15.9
sealing
Φ12.7
Φ6.4
Fig.1
MBB04
L5
L3
L4
D
Indoor unit
Table.2
Permitted
Piping
value
L1+L2+L3
≤100m
+L4+L5
L1+L2,L1+L3,
≤45m
L1+L4,L1+L5
L2,L3,L4,
≤20m
L5≤20m
≤20m
≤20m
≤8m
4.
THE WHOLE INSTALLATION INSTRUCTION
Thermal insulation
1
Connect to 1 - 4
set indoor unit
5.

INSTALLATION REQUIREMENTS

5.1.
Condensate discharge Installation
Level
a. All condensate discharge pipework must be insulated correctly.
b. To prevent condense water flowing back into the air conditioning
unit when the unit is off, ensure the condensate discharge pipework
is installed on a gradient of 1/100 or more with the directional flow
being away from the unit.
c. Condensate discharge pipework must be supported every 0.8 to
1.0 m.
5.2.
Minimum length of straight pipe
Outdoor unit
• The minimum length of straight pipe from the outdoor unit must be
>1m.
• The minimum length of pipework between the inlet of the mini
branch box and the closest change in direction must be >1m.
• The minimum length of pipework between the outlet of the mini
branch box and the closest change in direction must be >0.5m.
• The minimum length of pipework between the outlet of the mini
branch box and the closest change in direction must be >0.5m.
5.3.
Mini branch boxes must not be cascaded together
Thermal insulation
Hoisting bar
Connect to the
outdoor unit
Fig.3
Hosting ceiling
0.8-1.0m
Hosting bar
MBB04 box
Drain pipe
Fig.4
>1m
>0.5m
Fig.5
Fig.6
Gradient:higher
than 1/100
Indoor unit
CLIMATE 5000 VRF