Power Wiring Interconnections

NOTICE Improper installation could cause damage to the circuit
boards and shorten their life. Installing circuit boards in live
circuits will damage the board and is not covered by warranty.
ALWAYS disconnect ALL sources of power prior to servicing.
• Remove all power prior to installing this equipment. Failure to
do so could cause internal damage to the board when making
electrical connections.
• Turn generator to OFF position.
• Turn off utility power to the standby generator and
transfer switch.
All wiring must be the proper gauge, properly supported and
protected by conduit. All wiring should be done per applicable
federal, state and local codes, standards and regulations. Obey
wire type and torque specifications printed on the terminal blocks,
neutral/ground connectors, and installation instructions.
WARNING Shock Hazard. Installing low and high voltage
wire in same conduit could result in death or serious.
• Do not run low and high voltage wire in the same conduit unless
the insulation rating on ALL wiring is rated for 600V. See NEC
for more information.
Use installer supplied 600VAC or greater copper or aluminum wire
of a gauge that complies with the latest version of the National
Electric Code to complete the following connections between utility
power, transfer switch, generator, main distribution panel, and
optional remote modules. Apply the necessary correction factors
and wire size calculations.
1. Set generator's circuit breaker to OFF position.
2. Set generator's system switch to OFF position.
3. Remove 15 Amp fuse from generator control panel.
4. Turn off utility power to the standby generator and
transfer switch.
5. Connect utility service to transfer switch's utility
service disconnect circuit breaker terminals marked
"UTILITY CONNECTION".
6. Connect utility service neutral to transfer switch
neutral terminal.
7. Connect main distribution panel feeder conductors to transfer
switch terminals marked "LOAD CONNECTION".
8. NOTICE Connect main distribution panel neutral to transfer
switch neutral terminal.
WARNING Shock Hazard. Failure to properly wire equipment could
cause electrocution resulting in death or serious injury.
• DO NOT connect the ground conductor to the neutral connection in the
remote module.
• All modules must have a dedicated neutral connection.
11
44
9. Connect main distribution panel ground to transfer switch
"GND" terminal.
44
Generator
Circuit
0
Breaker
Ground
Ground
Line 1
To Transfer Switch
Assure grounding electrode conductor is connected and
bonded per applicable federal, state and local codes,
standards and regulations.
10. Connect feeder conductors from transfer switch breaker
"GENERATOR CONNECTION" terminals to generator circuit
breaker LINE1 and LINE2 terminals. Each conductor must
pass through hole of current transformer before
making connection.
11. Plug current transformer leads into "CT1" and "CT2"
terminals (C) on transfer switch control board.
J6
J5
J4
J3
J2
J1
240V
11
22
Neutral
Line 2
Neutral
C
11