Parám.
Descripción
P0295 Corriente Nominal ND/HD
del VFD
P0296 Tensión Nominal de la Red
P0297 Frecuencia de Conmutación
P0298 Aplicación
P0299 Tiempo Frenado Arranque
P0300 Tiempo Frenado Parada
P0301 Velocidad de Inicio
P0302 Tensión Frenado CC
Referencia Rápida de los Parámetros, Fallas y Alarmas
Rango de Valores
0 = 2 A / 2 A
1 = 3.6 A / 3.6 A
2 = 5 A / 5 A
3 = 6 A / 5 A
4 = 7 A / 5.5 A
5 = 7 A / 7 A
6 = 10 A / 8 A
7 = 10 A / 10 A
8 = 13 A / 11 A
9 = 13.5 A / 11 A
10 = 16 A / 13 A
11 = 17 A / 13.5 A
12 = 24 A / 19 A
13 = 24 A / 20 A
14 = 28 A / 24 A
15 = 31 A / 25 A
16 = 33.5 A / 28 A
17 = 38 A / 33 A
18 = 45 A / 36 A
19 = 45 A / 38 A
20 = 54 A / 45 A
21 = 58.5 A / 47 A
22 = 70 A / 56 A
23 = 70.5 A / 61 A
24 = 86 A / 70 A
25 = 88 A / 73 A
26 = 105 A / 86 A
27 = 105 A / 88 A
28 = 142 A / 115 A
29 = 180 A / 142 A
30 = 211 A / 180 A
31 = 2.9 A / 2.7 A
32 = 4.2 A / 3.8 A
33 = 7 A / 6.5 A
34 = 10 A / 9 A
35 = 12 A / 10 A
36 = 17 A / 17 A
37 = 22 A / 19 A
38 = 27 A / 22 A
39 = 32 A / 27 A
40 = 44 A / 36 A
41 = 53 A / 44 A
42 = 63 A / 53 A
43 = 80 A / 66 A
44 = 107 A / 90 A
45 = 125 A / 107 A
46 = 150 A / 122 A
0 = 200 / 240 V
1 = 380 V
2 = 400 / 415 V
3 = 440 / 460 V
4 = 480 V
5 = 500 / 525 V
6 = 550 / 575 V
7 = 600 V
0 = 1.25 kHz
1 = 2.5 kHz
2 = 5.0 kHz
3 = 10.0 kHz
4 = 2.0 kHz
0 = Uso Normal (ND)
1 = Uso Pesado (HD)
0.0 a 15.0 s
0.0 a 15.0 s
0 a 450 rpm
0.0 a 10.0 %
Ajuste de
Ajuste del
Propiedad Grupos Pág.
Fábrica
Usuario
De acuerdo con
el modelo del
convertidor
De acuerdo con
el modelo del
convertidor
0
0.0 s
0.0 s
30 rpm
2.0 %
ro
READ
6-5
cfg
6-6
cfg
6-7
cfg
6-8
V/f, V V W,
12-16
Sless
V/f, V V W,
12-16
Sless
V/f, V V W,
12-18
Sless
V/f, V V W
12-18
CFW701 | 0-9
0