11.6 TECHNICAL DATA
11.6.1 TecHNIcaL DaTa BT300
Function
Power supply:
Maximum pre fuse:
Power consumption:
Digital signal inputs:
Digital outputs:
Resolution:
Number of curve sets:
Number of programs:
Fieldbus-coupling (optional):
Housing:
Dimensions:
Weight:
Flammability:
Display
Display:
Dimensions:
Weight:
Housing:
Flammability:
230V +10/-15% 47-63Hz115V +10/-15% 47-63Hz (on request)
10A slow-blow
To be used only in a grounded power line network!
max. 30 VA
The parasitic capacity of the line connected to the digital inputs must
not exceed 2.2mF during the self-tests of the BT300.
Note: Max. line length 10m (see chapter 11.3 Connecting Diagrams)
3 fuel valves max. 1 A cos Φ 0,4
VL fan max. 2 A cos Φ 0,4
oil pump max. 2 A cos Φ 0,4
ignition transformer max. 2 A cos Φ 0,2
alarm output max. 1 A cos Φ 0,3
999 digit, 10 bit
BT320/330: 1 curve set (oil or gas)
BT340: 2 curve sets (oil / gas switchable; DFM300 or LCM100 necessary)
unlimited (EEPROM)
PROFIBUS
LCM100 always required
Polycarbonate + ABS
200x115x61mm
1,0kg
UL-94 V0 (panel: UL-94 V2)
128x64 pixel, monochrome
White background lightning (dimmable)
112x64x24
140g
Basic housing: Polyamide glass fibre reinforced LCD-display window: Polycarbonate
Basic housing UL-94 V0
LCD-display window UL-94 V2