On
Encoder/Inverter LED
On
Off
1 pause flash 1 flash
2 pause flash 2 flash
3 pause flash 3 flash
4 pause flash 4 flash
5 pause flash 5 flash
6 pause flash 6 flash
7 pause flash 7 flash
8 pause flash 8 flash
TABLE 10
Programming
LEDs on the
control unit
LED 1
Description
CLOSE
Off
During normal operation, it indicates "Automatic closure" not active.
On
During normal operation, it indicates "Automatic closure" active
OPEN
Flashes
• Programming of functions in progress.
PP
• If this flashes together with L2 this indicates that the device learning phase must be performed (see paragraph 3.12).
Quick flash
After control unit start-up, it indicates a memory error regarding the devices connected. At the same time, the "Bluebus" LED emits a
STOP
diagnostic signal: 5 flashes - pause of 1 second - 5 flashes. In this case it is necessary to carry out the learning phase of the connected
devices (see paragraph 3.12) or delete the memory (see paragraph 5.3.1).
ALT
LED 2
Description
Off
During normal operation, it indicates "Re-close after photo" not active.
BLUEBUS
On
During normal operation, it indicates "Re-close after photo" active.
Flashes
• Programming of functions in progress
• If this flashes together with L1, this indicates that the device learning phase must be performed (see paragraph 3.124.4).
Quick flash
After control unit start-up, it indicates a memory error regarding the positions. At the same time, the "Bluebus" LED emits a diagnostic
signal: 5 flashes - pause of 1 second - 5 flashes. In this case it is necessary to carry out the opening and closing learning phase (see
paragraph 3.13.5) or delete the memory (see paragraph 5.3.1).
LED 3
Description
Off
During normal operation, it indicates "Always close" not active.
On
During normal operation, it indicates "Always close" active.
Flashes
• Programming of functions in progress.
• If this flashes together with L4, this indicates that the learning phase of the opening and closing positions of the door must be
performed (see paragraph 3.12).
Quick flash
After control unit start-up, it indicates a memory error regarding the parameters and configurations. At the same time, the "Bluebus"
LED emits a diagnostic signal: 5 flashes - pause of 1 second - 5 flashes. In this case the memory must be deleted (see paragraph
5.3.1), and also the learnt connected devices (see paragraph 3.12) and learnt Opening and Closing positions (see paragraph 3.13).
LED 4
Description
Off
During normal operation, it indicates "compensation" not active.
On
During normal operation, it indicates "compensation" active.
Flashes
• Programming of functions in progress.
• If this flashes together with L3, this indicates that the learning phase of the opening and closing positions of the door must be
performed (see paragraph 3.13).
Quick flash
An error in the mains voltage reading has been detected or the braking board is missing. Turn off and on again: if the problem continues,
it might be necessary to replace the braking board.
LED 5
Description
Off
During normal operation, it indicates "Short deceleration" active.
On
During normal operation, it indicates "Long deceleration" active.
Flashes
Programming of functions in progress.
18
All OK
Cause
Failure
All Ok if operating with limit switch
All OK
Communication error with the inverter
Communication error with the encoder
- Inverter overcurrent protection activated
- Over/under current protection activated
Inverter over temperature protection activated
Overload protection activated
Protection activated from short circuit
Protection from interrupted wire activated
L1 L2
L3
L4 L5
L6 L7 L8
SAFE input active
Solution
Try to turn the board off and on again, if the problem continues replace
the board
Failure if operating with encoder or inverter
The communication with the encoder or the inverter works correctly
Check whether the cable is connected and the inverter is powered
Check whether the cable is connected and make sure it is not damaged
- Check whether there are obstacles on the door or in the gear reducer
of the motor inverter
- Check whether the line voltage is within the specifications, otherwise
stabilise the line voltage
Leave the inverter to cool down and decrease the operating cycle
Check whether there are obstacles on the door or in the gear reducer of
the motor with inverter
Replace the inverter braking resistance
Cut the power to the control unit, open the inverter and check whether
the phases of the motor are interrupted. In this case replace the motor
or check whether the motor inverter power supply cable has become
disconnected.