Descargar Imprimir esta página

WEG CFW700 Referencia Rápida página 23

Publicidad

Idiomas disponibles

Idiomas disponibles

Quick Parameter Reference, Faults and Alarms
Fault/Alarm
F0006:
The mains voltage imbalance is too
Input Voltage
high or phase loss at the supply line has
Imbalance or
occurred.
Phase Loss
Note:
- This fault may not occur if the load at
the motor shaft is too low or nonexistent.
P0357 sets the time for the trip, and
P0357 = 0 disables this fault.
F0021:
A DC link undervoltage condition has
DC Link
occurred.
Undervoltage
F0022:
A DC link overvoltage condition has
DC Link
occurred.
Overvoltage
A0046:
It is the motor overload alarm.
High Load at the
Note:
Motor
It can be disabled by setting
P0348 = 0 or 2.
A0047:
It is the IGBT overload alarm.
IGBT Overload
Note:
Alarm
It can be disabled by setting
P0350 = 0 or 2.
F0048:
It is the IGBT overload fault.
IGBT Overload
Fault
22 | CFW700
Description
Possible Causes
A Phase Loss at the inverter input.
The input voltage imbalance is > 5 %.
The input voltage is too low and the DC link voltage
dropped below the minimum permitted value
(monitor the P0004 parameter value):
Ud < 223 V - 200 / 240 V three-phase input
voltage.
Ud < 170 V - 200 / 240 V single-phase input
voltage (CFW700XXXXS2 or CFW700XXXXB2
models)
(P0296 = 0).
Ud < 385 V - 380 V input voltage (P0296 = 1).
Ud < 405 V - 400 / 415 V input voltage
(P0296 = 2).
Ud < 446 V - 440 / 460 V input voltage
(P0296 = 3).
Ud < 487 V - 480 V input voltage
(P0296 = 4).
Ud < 530 V - input voltage 500 / 525 V
(P0296 = 5).
Ud < 580 V - input voltage 550 / 575 V
(P0296 = 6).
Ud < 605 V - input voltage 600 V (P0296 = 7).
Phase loss at the inverter input.
Pre-charge circuit failure.
Parameter P0296 was set to a value higher than
the power supply rated voltage.
Too high input voltage, resulting in a DC link voltage
higher than the maximum permitted value:
Ud > 400 V - 220 / 230 V models (P0296 = 0).
Ud > 800 V - 380 / 480 V models
(P0296 = 1, 2, 3, or 4).
Ud > 1000 V - 500 / 600 V models
(P0296 = 5, 6 or 7).
The inertia of the driven-load is too high or the
deceleration time is too short.
The parameter P0151, P0153 or P0185 setting
is too high.
The settings of P0156, P0157 and P0158 are too
low for the used motor.
There is excessive load at the motor shaft.
The inverter output current is too high.
The inverter output current is too high.

Publicidad

loading