Quick Parameter Reference, Faults and Alarms
Fault/Alarm
A0177:
Fan replacement alarm
Fan Replacement
(P0045 > 50000 hours).
Note:
This function can be disabled by setting
P0354 = 0.
F0179:
This fault indicates a problem with the
Heatsink Fan
heatsink fan.
Note:
Speed Fault
This function can be disabled by setting
P0354 = 0.
F0182:
It indicates a fault in the output pulses
Pulse Feedback
feedback.
Fault
F0183:
Overtemperature related to the IGBT
IGBT Overload +
overload protection.
Temperature
F0185:
It indicates a fault at the pre-charge
Pre-Charge
contactor.
Contactor Fault
F0228:
Refer to the RS-232 / RS-485 Serial Communication Manual
Serial
Communication
Timeout
F0233:
Refer to the CANopen Communication Manual and/or the DeviceNet Communication Manual
CAN interface
without power
supply
F0234:
Bus Off
F0235:
Refer to the CANopen Communication Manual
CANopen
Communication
Error
F0236:
Refer to the DeviceNet Communication Manual
Idle Master
F0237:
DeviceNet
Connection
Timeout
F0238:
It indicates that the inverter received a
(2)
Profibus DP
command from the Profibus DP network
Interface in Clear
master to enter the clear mode.
Mode
F0239:
(2)
It indicates an interruption in the
Offline Profibus DP
communication between the Profibus DP
Interface
network master and the inverter.
F0240:
It indicates an error in the access to the
(2)
Profibus DP
Profibus DP communication module
Module Access
data.
Error
26 | CFW700
Description
Possible Causes
The heatsink fan maximum number of operating
hours has been reached.
Dirt on the blades and in the bearings of the fan.
Defective fan.
Defective fan power supply connection.
Defect in the inverter internal circuitry.
Inverter operating without motor.
Too high inverter surrounding temperature.
Operation with frequencies < 10 kHz with overload.
Defective pre-charge contactor.
Open command fuse.
Phase loss at the L1/R or L2/S input.
.
(3)
.
(3)
.
(3)
Verify the network master status, making sure it is
in the execution mode (Run).
The fault indication will occur if P0313 = 5.
Refer to the Profibus DP communication manual
for more information
.
(3)
Verify whether the network master is correctly
configured and operating normally.
Verify the network installation in a general manner
- cable routing, grounding.
The fault indication will occur if P0313 = 5.
Refer to the Profibus DP communication manual
for more information
.
(3)
Verify whether the Profibus DP module is correctly
fit into the slot 3.
The fault indication will occur if P0313 = 5.
Refer to the Profibus DP communication manual
for more information
.
(3)
.
(3)