I/O Expansion Modules
1. With the inverter powered down, remove its front
cover
(Figure A1 on page
2. Fit the accessory to be installed as shown in
A1 on page
3. Power up the inverter.

5 CONFIGURATIONS

The CFW100-IOA connections must be done to the I/O
expansion connector according to
The pins of the accessory connector are presented in
Figure A2 on page
Table 1: Signals of the I/O expansion connector
Counter-
Connector Description
clockwise
6
7
8
Clockwise
9
10
The location of switch S1.1 to select the type of signal
at the analog input can be better viewed in
on page
15. To use the analog input with voltage
signal, you must set switch S1.1 = OFF and related
parameters, for current input you set S1.1 = ON, as per
Table 2 on page
Switch S1.2, presented in
used to select the type of analog output. For a voltage
output you must set S1.2 = ON and related parameters,
for current output the switch is set S1.2 = OFF, as
presented in
refer to chapter 12 of the CFW100 programming manual.
6 | CFW100
14.
15.
GND
Reference 0 V Not interconnected with PE.
AI1
Analog
Input 1
+ 10 V
Reference
+ 10 V for
potentiometer
AO1
Analog
Output 1
GND
Reference 0V
7.
Table 2 on page
14).
Table 1 on page
Specifications
Isolated voltage input,
levels: (0 to 10) V or (0 to
20) mA or (4 to 20) mA.
Resolution: 10 bits.
Impedance: 100 kΩ for
voltage input and 500 Ω
for current input.
Programmable functions.
Maximum accepted
voltage: 30 Vdc.
Power supply: + 10 Vdc.
M a x i m u m c a p a c i t y :
50 mA.
Tolerance: ±5 %.
Insulated output, levels:
(0 to 10) V or (0 to 20) mA
or (4 to 20) mA.
Programmable functions.
R
≥ 10 kΩ (0 to 10 V) or
L
R
≤ 500 Ω (0 to 20 mA
L
/ 4 to 20 mA).
Not interconnected with PE.
Figure A2 on page
7. For further details,
Figure
6.
Figure A2
15, is