Table 2: Configurations of the connectors to select the type
of signal at the analog input and output on the CFW100-IOA
Input
Signal
Voltage
AI1
Current
Voltage
AO1
Current
NOTE!
The firmware version of the CFW100-IOA
accessory can be viewed in parameter P024
of the CFW100 inverter.
ATTENTION!
For the proper operation of the CFW100
inver ter with the CF W100-IOA module,
parameters P308, P310, P311 and P312 must
be programmed with the factory settings.
For further details, refer to the programming
manual of the CFW100 V2.3X or up.
Setting of
Switch S1
S1.1 = OFF
0 ... 20 mA
S1.1 = ON
4 ... 20 mA
S1.2 = ON
0 ... 20 mA
S1.2 = OFF
4 ... 20 mA
I/O Expansion Modules
Signal
Parameter
Range
Setting
0 ... 10 V
P233 = 0 or 2
P233 = 0 or 2
P233 = 1 or 3
0 ... 10 V
P253 = 0 or 3
P253 = 1 or 4
P253 = 2 or 5
CFW100 | 7