External voltage supply
Supply the communication module via the connection X210 by means of a separate supply
voltage.
Designation
+
−
For greater distances between the control cabinets, use a power supply unit in each control
cabinet.
Screw terminal data
Plug connector with screw connection
Possible connections
Tightening torque
Bare end
18
Explanation
External voltage supply
U = 24 V DC (20.4 V − 0 % ... 28.8 V + 0 %)
I = 140 mA
Reference potential for external voltage supply
rigid: 1.5 mm
flexible:
without wire end ferrule
1.5 mm
with wire end ferrule, without plastic sleeve
1.5 mm
with wire end ferrule, with plastic sleeve
1.5 mm
0.5 ... 0.6 Nm (4.4 ... 5.3 lb−in)
6 mm
l
2
(AWG 16)
2
(AWG 16)
2
(AWG 16)
2
(AWG 16)