Unscheduled Maintenance; Troubleshooting - Sime Brava One BF Manual De Instalación Y Mantenimiento

Calderas murales de baja temperatura
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

EN
4.5

Unscheduled maintenance

If replacing the electronic board , the user MUST set the
parameters as indicated in the table.
Type
Nr.
Description
Index showing boiler power
tS
0.1
in kW
0 = 24; 1 = 30
Hydraulic configuration
0 = rapid
1 = storage tank with
thermostat or heating only
tS
0.2
2 = hot water tank with sensor
3 = two programmer
4=instant with solar power
input
Gas Type Configuration
tS
0.3
0 = G20; 1 = G31
Combustion configuration
0 = sealed chamber with
combustion control
tS
0.4
1 = open chamber with smoke
thermostat
2 = low NOx
To enter "Parameter setting and display"refer to the indications
provided in the specific section.
Once the parameters in the table have been set, you must carry
out the "Automatic calibration procedure".
If the gas valve and/or the ignition/detection electrode and/or the
are replaced, the user must still carry out the entire phase
fan
of "Automatic calibration procedure" described in the specific
section.
4.6

Troubleshooting

LIST OF MALFUNCTION/FAULT ALARMS
Type
Nr.
Fault
Low water pressure
AL
02
in system
Domestic hot water
AL
04
sensor fault
Delivery sensor
AL
05
fault
AL
06
No flame detection
Sensor or safety
AL
07
thermostat
intervenes
Fault in the flame
AL
08
detection circuit
No water
AL
09
circulating in the
system
Setting for
Brava
One BF
25
30
0
1
0
0 or 1
0
Solution
- Restore pressure
- Check for any leaks in the
system
- Check connections
- Replace the sensor
- Check connections
- Replace the sensor
- Check the integrity of the
electrode and check that it is
not grounded
- Check gas availability and
pressure
- Check the integrity of the gas
valve and the card
- Check the sensor or
thermostat connections
- Deaerate the system
- Check the bleed valve
- Replace the sensor or the
thermostat
- Check that the pump
impeller is not blocked
- Check the integrity of the
electrode and check that it is
not grounded
- Check gas availability and
pressure
- Check the integrity of the gas
valve and the card
- Check the rotation of the
system pump impeller
- Check the electrical
connections
- Replace the pump
Type
Nr.
Fault
Gas valve modulator
AL
11
disconnected
Incorrect
configuration of
AL
12
the open /sealed
chamber
Fault regarding
maximum deviation
AL
17
between the 2 NTC
heating sensors
Maximum number
AL
28
of consecutive
resets reached
Fault due to low
AL
37
network voltage.
Incorrect network
AL
40
frequency detected
Flame loss more
AL
41
than 6 consecutive
times
AL
42
Button fault
Open Therm
AL
43
communication
fault
The self-calibrating
AL
62
procedure must be
carried out
Incorrect
AL
72
positioning of the
delivery sensor
Fault in the 2nd
AL
74
element of the
delivery sensor
Block due to
AL
81
combustion during
start-up
Irregular
AL
83
combustion
(temporary error)
Block due to
AL
96
clogging in smoke
outlet
Frequent relief
-
-
valve intervention
Limited production
-
-
of domestic hot
water
Solution
- Check the electrical
connection
- Set the parameter tS 0.4
(Combustion configuration)
to 0
- Replace the dual sensor
- Contact the Technical
Assistance Centre
- Check with tester
- Contact network provider
(ENEL)
- Contact network provider
(ENEL)
- Check the detection
electrode
- Check the gas supply (open
valve)
- Check mains gas pressure
- Check that buttons are
working
- Check the electrical
connection of the remote
control
- Carry out the self-calibrating
procedure (see the specific
section)
- Check that the delivery
sensor is attached to the
delivery pipe
- Replace the sensor
- Check for blockage in
chimney
- Bleed the air from the gas
circuit
- Check for blockage in
chimney
- Check for blockage in
chimney
- Check circuit pressure
- Check expansion vessel
- Check the diverter valve
- Check that plate heat
exchanger is clean
- Check domestic hot water
circuit valve