Wiring The Grafik Eye Qs System; Class 2 / Pelv Cable - Lutron GRAFIK Eye QS System Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Wiring the GRAFIK Eye
Class 2 / PELV USA Cable
IR Wiring
1,0 mm
2
(#18 AWG)
each terminal
From external
IR connection
(by others)
Occupant Sensor Wiring
1,0 mm
2
(#18 AWG)
each terminal
Occupant
sensor
Control Wiring
Common and power (terminals 1 and 2):
Two 1,0 mm
2
(#18 AWG) each terminal
To control stations,
window treatments, or
other GRAFIK Eye QS
control units
Data (terminals 3 and 4):
Twisted, shielded pair 1,0 mm
each terminal
Note: Use appropriate wire connecting devices as
specified by local codes.
R
QS System
®
1: IR DATA
2: IR COM
A: OCC SIG
B: 24 V
C: OCC COM
1: COM
2: 24 V
3: MUX
4: MUX
2
(#22 AWG)
Line Voltage/Mains Cables
and Load Wiring
2,5 mm
2
(#12 AWG)
each terminal
To Load 1
To Load 2
To Load 3
To Load 4
To Load 5
To Load 6
GRAFIK Eye
QS System Installation and Operation Guide 4
®
1 2 3 4 5 6 L N
1 2 3 4 5 6 L N
L N
230 V
Distribution Panel