TECHNICAL DATA

E
N
G
THERMIC CAPACITY
L
I
FLOW RATE
S
MINIMUM PRESSURE (*)
H
NATURAL GAS TRANSFORMER
THERMIC CAPACITY
FLOW RATE
FUEL VISCOSITY
LIGHT OIL TRANSFORMER
VOLTAGE
FAN MOTOR
PUMP MOTOR
STANDARD ACCESSORIES
BURNER FIXING FLANGE
INSULATING GASKET
FILTER
FLEXIBLE PIPE
NIPPLE
STUD BOLTS
EXAGONAL NUTS
FLAT WASHERS
TECHNICALAND FUNCTIONALCHARACTERISTICS
• Alternate natural gas/light oil burner.
• Two-stage progressive output operation.
• Ability to operate with output modulation by means of automatic
RWF40 regulator mounted on the control panel (to be ordered
separately with the modulation kit).
• Ability to operate with any type of combustion chamber.
• Air-gas mixing at blast-pipe and high pressure mechanical atomi-
sation of fuel using nozzle.
• Ability to obtain optimal combustion values by regulating combu-
stion air and blast-pipe.
COMIST
72 DSPGM
122 DSPGM
916
MAX
kW
348
MIN
kW
92
MAX
m³/h
35
MIN
m³/h
24
CE mbar
916
MAX
kW
348
MIN
kW
77
MAX
kg/h
29
MIN
kg/h
10 kV - 20
mA
Volt
1,1 - 2950
2,2 - 2950
kW / r.p.m
0,55 - 1420
kW / r.p.m.
1
1"
N°2 - 1"x1"
N°1 - 1"x1"
N°4 M12
N°4 M12
N°4 Ø12
• Maintenance facilitated by the fact that the mixing unit and the
atomisation unit can be removed without having to remove the
burner from the boiler.
• Minimum and maximum air flow regulation for first and second
stage by means of electric servomotor with pause closure of gate
to prevent any heat dispersion to flue.
• A valve tightness control can be fitted on the burner.
• Prepared for automatic fuel switching.
4 / 30
0006080115_200909
COMIST
COMIST
COMIST
180 DSPGM
250 DSPGM
1364
1981
652
688
137
199
66
69
23
39
8 kV - 20 mA
1364
1981
652
688
115
167
55
58
1,5°E a/at 20°C
12 kV - 30 mA
3N - 230/400V - 50Hz
3 - 2870
0,75 - 2800
1
1"1/4
N°2 - 1"¼x1"¼
-
-
N°6 M20
N°6 M20
N°6 Ø20
COMIST
300 DSPGM
3380
3878
1127
1304
340
390
113
131
105
140
3380
3878
1127
1304
285
327
95
110
14 kV - 30 mA
7,5 - 2870
1,5 - 2800
2
-
-
N°4 M16
N°4 M16
N°4 Ø16

Publicidad

loading

Este manual también es adecuado para:

Comist 122 dspgmComist 180 dspgmComist 250 dspgmComist 300 dspgm