(2)Select the suspension bolt locations and the pipe
hole location.
·
Place the left hanger bracket on the nuts and
washers of the suspension bolts.
·
Make sure that the left hanger bracket has been
fixed on the nuts and washers securely, install the
right hanger bracket suspension hook on the nuts
and washers.
(When installing the indoor unit, you can slightly
remove the suspension bolts.)
(3) Fix with 4 suspension bolts,which can endure
load of 530N.
(4) Check the measurements the length of the
suspension bolts.
(5) Fasten the hanging plate onto the suspension
bolts.
(6) Install the unit to the hanging plate.
i.Slide the unit from front side to get it hanged on the
hanging plate with bolts.
ii.Fasten the four fixing bolts(M8:2 each on the left
and right sides)firmly.
iii.Fasten the two screws(M5:1 each on the left and
right sides.)
Hanging plate
Ceiling
Hanging plate
Suspension bolt
Fig. 3.3.8
Hanging plate
fixing bolts(M8)
Hanging plate
screw (M5)
Fig. 3.3.9
Installation and Maintenance
Floor standing type installation
(1)Select the suspension bolt locations and the pipe
hole location.
i
.Use enclosed paper pattern as a reference ,and drill
the holes for the suspension bolts and pipe.
Note:
Decide the locations based on the direct
measurements.
ii.After the locations are properly placed, the paper
pattern can be removed.
2).Install the suspension bolts in place.
Wall
Floor
(2) Fix with 4 suspension bolts, and fasten the four
fixing bolts(M8:2 each on the left and right
sides)firmly.
(3).Fasten the two screws of Air Intake Grille(M5:1
each on the left and right sides).
3.3.5 The horizon adjustment of the indoor unit
(1) Make sure that the hanger bracket is fixed by the
nut and the washer.
(2) Adjust the height of the unit.
(3) Check the unit is horizontally level.
*To ensure smooth drain flow,install the unit with a
descending slope(0-3mm) toward the drain outlet.
(4) After the adjustment, tighten the nut and swear the
thread locker on the suspension to prevent the nuts
from loosening.
CAUTION
During the installation, please cover the unit with the
plastic cloth to keep it clean.
13
Pattern board
Fig. 3.3.10