LIGHT OIL BURNER
MODEL SPARK

USE OF THE BURNER

The burner operates fully automatically, therefore it is non necessary to carry out any kind at
adjustment during its operating.
The "block" position is a safety position reached by the burner automatically when some of the
components of the burners or the plant do not work properly. It is necessary to check then whether
the cause to the problem is a dangerous one before unblocking the burner.
The causes to the block may be temporary, for example when air in inside the pipes.
When it is unblocked, the burner starts operating properly.
If the burner stops three or four times at a stretch, it is necessary either to loock for the problem and
solve it or ask for the intervention of the after sales service.
The burner can remain in the "block" position without any limit in time.
In emergency cases it is advisable to close the fuel valve, and disconnect the burner electrically.
MAINTENANCE
At the end of the heating season, it is usually advisable to clean the filter, blast tube (disc, insulators,
electrodes, nozzles), combustion air passages and photoconductive cell.
To clean nozzle passages, use soft material (e.g.wood,plastic).
Replacement of nozzles every 12 months of operation is recommended.

SAFETY CHECKS

Checks the following:
1) Burner stoppage by opening the thermostats;
2) "Blocking" by shading the photoconductive cell.
To unblock push the appropriate button.