8. Connection of the auxiliary power and ground connection

Before starting the auxiliary power supply connection process, check that the wiring hose is
disconnected from the power source.
Enter the corresponding hose to the auxiliary power supply via the packing gland closest to terminal X01.
We recommend leaving a small hose loop (4 ~ 5 cm radius) within the unit before cutting the hose to the
corresponding distance.
Once the hose is cut, peal the last 10 cm section to strip the power cables to their individual insulation.
After uncovering the cables, cover the end of the hose together with the start of the individual cables with
a heat-shrink plastic of 4 ~ 5 cm.
Loosen the X01 terminal screws from below the terminal.
Strip the last 1 cm of the cables and insert them into the X01 terminal in the following order (from left to
right):
1.
Phase
2.
Neutral
3.
Ground
Tighten the X01 terminal screws again once the bare wires have been entered.
Lift the cover of the lower cable entrances and insert the hose into it, so that the hose goes in the lower
side, and in the upper part 3 individual wires come out to the X01 terminal.
20
Connection of the auxiliary power and ground connection
ABP2011IQM01_ - Installation and Operation Manual