1550C/1555
Users Manual
Electromagnetic
Compatibility
Certifications
Safety Compliance
Pollution Degree
Typical Battery Charge
Capability
Note
At temperature extremes, the
battery needs to be charged
more frequently.
Electrical Specifications
The Tester's accuracy is specified for 1 year after calibration at operating
temperatures of 0 °C to 35 °C. For operating temperatures outside the range (-
20 °C to 0 °C and 35 °C to 50 °C), add ±0.25 % per °C, except on the 20 %
bands add ±1 % per °C.
Test Voltage (DC)
250 V
500 V
30
EN 61326-1, EN 61326-2-2
P ® )
EN 61010-1, EN 61557 Parts 1 and 2
CAT III 1000V, CAT IV 600V
2
Test Voltages
250 V
500 V
1 kV
2.5 kV
5 kV
10 kV
Insulation
Insulation Resistance Range
< 200 kΩ
200 kΩ to 5 GΩ
5 GΩ to 50 GΩ
> 50 GΩ
< 200 kΩ
200 kΩ to 10 GΩ
10 GΩ to 100 GΩ
> 100 GΩ
Number of Tests
4100
3600
3200
2500
1000
500
Accuracy (±reading)
unspecified
5 %
20 %
unspecified
unspecified
5 %
20 %
unspecified