8 - Predefined Application Setup
App
Mode
Cooling/
App 0
Heating
App 1
Cooling
App 2
Cooling
App 3
Cooling
App 4
Cooling
App 5
Cooling
Cooling/
App 6
Heating
DI1 DI2
230
Vac
DO1
| 14
Description
None (no preset application)
Medium temperature ventilated refrigeration units with timed
natural defrost
Medium temperature ventilated refrigeration units with timed
electrical defrost
Low temperature ventilated refrigeration units with timed
electrical defrost
Medium temperature ventilated refrigeration units with
electrical defrost (by temperature)
Low temperature ventilated refrigeration units with electrical
defrost (by temperature)
None (no preset application) with simplified parameter list
APP 1
Sair
DO2 DO3
Instruction sheet | ERC 213
APP 2/3
DI1 DI2
230
Vac
DO1
DO2
DO3
Temp.
Def. type
(2 – 6 °C)
Natural
(0 – 4 °C)
Electrical
(-26 – -20 °C) Electrical
(0 – 4 °C)
Electrical
(-26 – -20 °C) Electrical
APP 4/5
Sair
230
Vac
DO1
DKRCC.EI.RL0.G2.ML/520H9654
Def. end
Time
Time
Time
Temperature
Temperature
DI1 DI2 S5
Sair
DO2
DO3