Connecting The Regulator - Sincro SK 400 Manuale Di Uso E Manutenzione

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

6.4.4.2 Connecting the regulator

Five position faston terminal
PE - Earth Connection
L, N - Power AVR (made with an auxiliary winding in the
stator, or integrated with a PMG)
Ex +, Ex - Power Exciter stator.
Nine position faston terminal
A, B, C: The reference voltage can be single or three
phase. For the reference voltage threephase use all three
connectors, single-use reference to either terminal A or B
while the C terminal is always connected.
S3, S4: on these two connectors, you can apply a
potentiometer (20 kΩ, ½ W) to adjust the voltage (place
the jumper (J6) in the position Pot). To set S3 and S4 as
analog input (0 to 3 Vdc, 0 ÷ 5 Vdc, 0 to 10 Vdc), place
the jumper (J6) in the position Volt.
To calibrate the voltage range under the condition of the
analog signal, turn the trimmer fully counterclockwise in
V (the voltage of the alternator will be at the minimum
value)
Apply on the connectors S3 and S4 half of the maximum
value of the analog signal, with the trimmer calibrating the
voltage V. Example: Analog signal 0 to 5 V, to adjust to 400
V, applied to S3 and S4 a signal of 2.5 V (+2.5 V = S3, S4 =
0 V) with V trimmer to adjust the alternator voltage of 400 V.
Terminals D-, D + and Vb are used for connecting the
controller with the software AVRTerm.
Jumpers
The jumper J1-J2-J3-J4 identify the frequency of rotation of
the machine, the voltage to be monitored by the regulator
and the type of sensing, single or three phase (refer to
table below).
Jumper J5: select the system to feed the AVR.
Jumper J6: select
VOLT / pot (analogic input / external
potentiometer).
Trimmer
Trimmer
V: Voltage adjustment or adjustment analogic input
control.
S: Stability adjustment.
According to the voltage and frequency, the AVR must be
confi gured as a side table:
AVR SENSING JUMPERS CONFIGURATIONS
J1
J2
J3
• •
• •
• •
• •
• •
• •
• •
• •
• •
If the voltage is set any higher than its
maximum limit the generator may be
damaged.
CAUTION!
Further adjustments are possible with use the AVR TERM
software.
ENGLISH
VOLTAGE
J4
PHASES
/ FREQ.
50Hz
60Hz
400V
3p
• •
430V
3p
230V
3p
• •
115V
3p
400V
1p
280V
1p
230V
1p
• •
115V
1p
25