Connector (N.O.) radio and/or pushbutton
(Jumper desabled).
See DIP 2-3 for command type
2-7
Button operation: closure only (Jum-
per enabled)
N.B. A bridge connection must be applied across all N.C. contacts and pushbutton not used.
Selection functions
c
10-WAY DIP-SWITCH
1 ON
Automatic closure enabled;
2 ON
"Open/close/reverse" radio control or pushbutton function enabled;
2 OFF "Open/stop/close/stop" radio control or pushbutton function enabled;
3 ON
"Only open" radio control function enabled;
4 ON
Pre-fl ashing (opening and closing) enabled;
5 ON
Obstacle detection device enabled;
6 ON
"Operator present" operation enabled; (radio remote control is deactivated when function is selected)
7 ON
Hammer movement operation enabled; (this function helps unlock the electric lock)
8 OFF "Partial-stop" enabled; insert the safety device on terminal 2-C3 (if not used, set the dip-switch to ON)
9 OFF "Stop" button enabled; insert the safety device on terminal 1-2 (if not used, set the dip-switch to ON)
10OFF Re-opening in closing phase enabled; insert the safety device on terminal 2-C1 (if not used, set the dip-switch to ON)
d
4-WAY DIP-SWITCH
1
Must stay OFF
2
Must stay OFF
3 ON
Activates safety test that checks the photocells proper operation.
4
Not used
10
JUMPER n°20
JUMPER n°20
The data and information provided in this manual are to be considered susceptible to change at any time without warning, by CAME cancelli automatici s.p.a.